Plan Review Notes
Plan Review Notes For Permit 17101162
Permit Number 17101162
Review Stop B
Sequence Number 1
Notes
Date Text
2017-10-31 10:44:23****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 1. PERMIT VALUE HAS BEEN REVISED TO INCLUDE ALL SUB
 CONTRACTORS . IT NOW IS $201,800.
  
 2. INCLUDED IN THE BUILDING DATA IS THE LEVEL OF
 ALTERATION AS "REPAIRS". SEE EXISTING BUILDING CODE
 SECTIONS 503 AND 504 FOR LEVEL 1 AND 2 ALTERATIONS.
 SHOW HOW COMPLIANCE WITH THE SELECTED LEVEL OF
 ALTERATION WILL BE SELECTED.
  
 3. A) A1.1 LEGEND NOTE, NEW WALL SEE A.0.3 FOR
 PARTITION DETAILS. PAGE A0.3 NOT PROVIDED WITH THESE
 PLANS.
 B) A1.1 LEGEND NOTE, SEE A7.1 FOR DOOR SCHEDULE. PAGE
 A7.1 NOT PROVIDED WITH THESE PLANS.
  
 4. PROVIDE AN EVALUATION REPORT FOR THE CLOSED CELL
 INSULATION USED. SHOW HOW THIS PRODUCT WILL BE IN
 COMPLIANCE IN TYPE I CONSTRUCTION FBC 2603.5 AND FBC
 2605.1. ALSO FOR FLAME SPREAD AND SMOKE-DEVELOPED
 INDEXES. FBC 2605.5.4.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  