| Plan Review Notes For Permit 17101134 |
| Permit Number |
17101134 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-03 12:10:12 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17101134 | | | 11/3/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REFER TO 513 SMOKE CONTROL SYSTEMS, AND SPECIFICALLY | | | SECTIONS 513.10, AND 513.10.5. VERIFY THAT THE NEW | | | GREENHECK TFI-FS FAN IS RATED AND CERTIFIED BY THE | | | MANUFACTURER FOR THE PROBABLE TEMPERATURE RISE, IS UL | | | LISTED AS A POWER VENTILATOR FOR SMOKE CONTROL, AND | | | THAT IT IS EQUIPPED WITH TWO BELTS. | | | | | | 2) SHEET M3.1) PROVIDE THE WIND LOAD DESIGN CRITERIA | | | PER SECTION 1609 FBC-14 BUILDING. | | | | | | 3) M4.1) THE SHEET IS TOO FAINT TO READ AND NOT | | | LEGIBLE- SECTION 107.1 WPB AMENDMENTS TO THE FBC. | | | | | | 4) VERIFY THE FAN IS BEING SUPPLIED WITH TWO SOURCES OF | | | POWER- PRIMARY FROM THE NORMAL BUILDING SYSTEM, AND | | | SECONDARY FROM AN APPROVED STANDBY SOURCE- SECTION | | | 513.11. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|