| 2017-10-31 11:42:13 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17101133 |
| | W. P. B. PERMIT: 16110007 |
| | ADD: 901 45TH ST. |
| | CONT: PROVINCIAL SOUTH DBA PSI ROOFING |
| | TEL: 954-791-7663X225 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. OCT. 31/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE UNDER THE ORIGINAL PERMIT THE ONLY |
| | STRUCTURAL SHEETS THAT WERE SUBMITTED ARE S-000, S-100 |
| | & S-101. WE HAVE NO RECORDS OF A SHEET S-102. PLEASE |
| | SUBMIT SHEET S-102 AS A REVISION NOTE ADDITIONAL REVIEW |
| | AND ASSOCIATED COST. 107.2.1.3 ADDITIONAL DATA. |
| | |
| | 2) PLEASE NOTE THE PLANS DRAWINGS APRON ROOF DETAIL |
| | DUEL CONCRETE/ STEEL SUBSTRATE DO NOT HAVE WHO THE |
| | AUTHOR OF THE PLANS IS, IF THE CONTRACTOR, WHICH |
| | ROOFING OR THE CGC, IS THIS OUT OF THE SCOPE OF THE |
| | CONTRACTING LICENSING LAWS? IF NOT THE QUALIFIER WILL |
| | NEED TO PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE |
| | NUMBER, OTHERWISE A DESIGN PROFESSIONAL WILL NEED TO |
| | SIGN AND SEAL THE PLAN. PLEASE NOT IF THE CONTRACTOR |
| | TAKES RESPONSIBILITY FOR THE PLANS THEN IT WILL NEED TO |
| | BE REVIEWED BY THE DESIGN PROFESSIONAL AND SHOP DRAWING |
| | STAMP OF APPROVAL APPLIED. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN |
| | CODE 61G16.003(1) ARCHITECTS. |
| | |
| | 3) PLEASE NOTE THE STRUCTURAL ENGINEER OF RECORD HAS |
| | NOT REVIEWED THE SHOP DRAWINGS APRON ROOF DETAIL DUEL |
| | CONCRETE/ STEEL SUBSTRATE NOR HAVE THEY REVIEWED THE |
| | ROOFING PRODUCT APPROVAL AND AFFIXED THEIR SHOP DRAWING |
| | STAMP OF APPROVAL. |
| | |
| | 4) COMPLIED. PLEASE NOTE THE ROOFING APPROVAL NOA |
| | 14-0220.08 SUB-SYSTEM TPO DECK TYPE 2 PAGES 58&59HAVE |
| | HIGHLIGHTED FASTENING OPTION # 3 WITH A MAXIMUM DESIGN |
| | PRESSURE OF -67.5 PSF AND LIMITATION # 7 ALLOWING FOR |
| | ENHANCED FASTENING FOR ROOF ZONE # 3. |
| | |
| | FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |