| Plan Review Notes For Permit 17101121 |
| Permit Number |
17101121 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-27 11:15:40 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF PRODUCT APPROVALS AS REQUIRED BY | | | FBC 107.1. ONLY ONE SET WAS SUBMITTED. | | | | | | 2) SPECIFY THE ROOF SLOPE, MEAN ROOF HEIGHT AND AREA OF | | | THE ROOF THAT IS BEING REPLACED. FBC 107.2.1 | | | | | | 3) SUBMIT TWO COPIES OF A DIAGRAM OF THE ROOF AND | | | IDENTIFY THE AREAS THAT WILL BE RE-ROOFED. FBC 107.2.1 | | | |
|