| 2018-01-18 09:04:48 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17101112 |
| | 1/18/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1: IT IS ACKNOWLEDGED THAT THE REQUIRED |
| | SOURCE CAPTURE SYSTEMS FOR THE MANICURE AND PEDICURE |
| | STATIONS HAS BEEN PROVIDED, HOWEVER THE REQUIRED BEAUTY |
| | SALON EXHAUST VENTILATION SYSTEM HAS NOT BEEN PROVIDED |
| | AS WAS PREVIOUSLY REQUESTED- SEE TABLE 403.3. PLEASE |
| | NOTE THE FOLLOWING: THERE ARE TWO OUTSIDE AIR |
| | CALCULATION TABLES ON M-1. THE NEW TABLE ACCURATELY |
| | |
| | INDICATES 0.60 CFMS OF EXHAUST AIR REQUIRED FOR THE |
| | BEAUTY SALON AND SKIN CARE AREAS, HOWEVER THE OTHER |
| | TABLE INCCURATELY SPECIFIES AN OUTSIDE AIR (FRESH AIR) |
| | RATE OF 0.60 CFMS FOR OCCUPANTS. PLEASE CORRECT THIS |
| | CONFLICT AND PROVIDE THE SALON EXHAUST SYSTEM. |
| | |
| | 2) M-1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN |
| | AIR SYSTEMS OF AHU-1 & 2- SECTION 606.2.1. |
| | |
| | 3) ADVISORY: APPROVED SHOP DRAWINGS FOR THE CHILLED |
| | WATER SUPPLY AND RETUN PIPING SHALL BE ONSITE AT TIME |
| | OF INSPECTION. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |