| 2017-11-16 10:52:41 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. EXISTING GUTTER WIREWAY DOES NOT SHOW WIRE SIZES. |
| | PROVIDE DETAILS FOR WIRE SIZE FEED AND OCP TO THIS |
| | WIREWAY. NEC 215.2, 215.5, 240.4 |
| | 2. PROVIDE LOAD CALCULATION FOR EXISTING GUTTER WIREWAY |
| | TO DETERMINE THAT THE SERVICE IS ADEQUATE TO HANDLE THE |
| | ADDITIONAL LOAD. NEC 220 |
| | 3. PROVIDE AIC RATING OF SERVICE DISCONNECT. NEC 110.3, |
| | 110.9 |
| | 4. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| | CURRENT AT DISCONNECT AND NEW PANEL TO CONFIRM AIC |
| | RATING IS ADEQUATE. NEC 110.10 |
| | 5. PROVIDE ACCURATE LOAD CALCULATION. THE PROVIDED |
| | CALCULATION IS PERMITTED FOR A RESIDENCE ONLY, NOT FOR |
| | COMMERCIAL BUILDINGS. PROVIDE CORRECTION. NEC 220; FBC |
| | 107.2.1 |
| | 6. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| | ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| | CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| | CODE. FBC CE 405.5 |
| | 7. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| | AUTOMATIC CONTROL REQUIRED. FBC CE 405.2.2, 405.2.2.2 |
| | 8. WILL THERE BE ANY SHOW WINDOWS? PROVIDE SHOW WINDOW |
| | OUTLETS IF NECESSARY. NEC 210.62 |
| | 9. PROVIDE GFCI PROTECTION FOR ANY OUTLETS WITHIN 6 |
| | FEET OF WATER. EXAMPLES INCLUDE THE HAIR WASH, PEDICURE |
| | CHAIR AND AREA, AND MANICURE AREAS. NEC 210.8 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |