2018-02-28 08:37:103RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 PERMIT #17101103
 2/28/18
  
 PLAN REVIEW RESULTS:
  
 1) THE ENERGYGAUGE COMPLIANCE FORMS:
  
 A) THE FORMS ARE MISSING THE CERTIFICATION SIGNATURES
 OF THE OWNER/AGENT AND THE DESIGN PROFESSIONAL WHO
 PREPARED THE CALCULATIONS. PLEASE SEE PAGE 3 OF THE
 FORMS AND SECTION C103.1.1.2 FBC-14 ENERGY CONSERVATION
 AND PROVIDE SIGNED AND DATED FORMS.
  
 B) MISSING FROM THE ENERGY FORMS ARE THE INPUT DATA
 REPORTS- SEE PAGE 1 ON THE FORMS.
  
 C) THE DESIGNER WHO PREPARED THE ENERGY FORMS MUST
 COMPLETE THE MANDATORY REQUIREMENTS CHECKLIST ON PAGE 7
 OF THE FORMS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  