| Plan Review Notes For Permit 17101103 |
| Permit Number |
17101103 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-02-28 08:37:10 | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | | PERMIT #17101103 | | | 2/28/18 | | | | | | PLAN REVIEW RESULTS: | | | | | | 1) THE ENERGYGAUGE COMPLIANCE FORMS: | | | | | | A) THE FORMS ARE MISSING THE CERTIFICATION SIGNATURES | | | OF THE OWNER/AGENT AND THE DESIGN PROFESSIONAL WHO | | | PREPARED THE CALCULATIONS. PLEASE SEE PAGE 3 OF THE | | | FORMS AND SECTION C103.1.1.2 FBC-14 ENERGY CONSERVATION | | | AND PROVIDE SIGNED AND DATED FORMS. | | | | | | B) MISSING FROM THE ENERGY FORMS ARE THE INPUT DATA | | | REPORTS- SEE PAGE 1 ON THE FORMS. | | | | | | C) THE DESIGNER WHO PREPARED THE ENERGY FORMS MUST | | | COMPLETE THE MANDATORY REQUIREMENTS CHECKLIST ON PAGE 7 | | | OF THE FORMS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|