| Plan Review Notes For Permit 17101103 |
| Permit Number |
17101103 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-12-28 08:20:19 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | | CODES | | | PERMIT #17101103 | | | 12/28/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE REQUESTED ENERGY COMPLIANCE REPORT WAS NOT | | | SUBMITTED. PLEASE SEE SECTION C101.4.4 FBC-14 ENERGY | | | CONSERVATION AND RESPOND ACCORDINGLY. | | | | | | 2) SHEET H.1: IN RESPONSE TO COMMENT #4 FROM THE 1ST | | | REVIEW, THE ARCHITECT IS INDICATING THAT EACH OF THE | | | 4-TON SYSTEMS WILL PRODUCE 1600 CFMS, HOWEVER THE AC | | | LAYOUT PLANS ARE SHOWING AHU-1 PRODUCING 640 CFMS, | | | AHU-2- 610 CFMS, & AHU-3- 500 CFMS. PLEASE PROVIDE AC | | | LOAD CALCULATIONS TO VERIFY CORRECT SIZING OF THE | | | SYSTEMS- SEE SECTIONS C403.2.1 & C403.2.2. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|