Plan Review Notes
Plan Review Notes For Permit 17101103
Permit Number 17101103
Review Stop E
Sequence Number 2
Notes
Date Text
2018-01-03 10:47:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL 2ND REVIEW STATUS: DENIED, SEE COMMENTS
 BELOW. PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE
 BEEN REMOVED.
  
 1. PANEL B SHOWS A LOAD OF 197.5 AMPS, BUT THE LOAD
 CALCULATION DOES NOT INCLUDE THE 25% ADDITIONAL LOAD
 REQUIRED FOR CONTINUOUS LOADS. THE RTU'S ARE CONSIDERED
 A CONTINUOUS LOAD. THE CONDUCTORS FEEDING THIS PANEL,
 AND THE OVERCURRENT PROTECTION OF THE PANEL WOULD NEED
 TO BE A SUM OF 125% OF THE CONTINUOUS LOAD PLUS 100% OF
 THE NON-CONTINUOUS LOAD. THE PANEL NEEDS TO BE RATED TO
 HANDLE THIS LOAD. PROVIDE CORRECTION. NEC 215.2, 215.3,
 408.30, 408.36
 2. THE AIC RATINGS LISTED ON THE PANEL SCHEDULES IS
 SHOWN AS 10,000 AIC. THE SHORT CIRCUIT CALCULATION
 PROVIDED SHOWS A MINIMUM RATING OF 14,119 AMPS IS
 REQUIRED. PROVIDE CORRECTION. NEC 110.9
 3. PANEL SCHEDULES STATE THAT THE PANELS ARE 3 PHASE, 3
 WIRE, WHICH IS INCORRECT. PROVIDE CORRECTION TO SHOW
 PANELS AS SINGLE PHASE. NEC 110.3; FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  