Plan Review Notes
Plan Review Notes For Permit 17101103
Permit Number 17101103
Review Stop B
Sequence Number 2
Notes
Date Text
2018-01-04 11:53:052014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17101103
 ADD: 538 NORTHWOOD RD.
 CONT: AUTHORIZED ADVANCED GENERAL CONTRACTORS INC.
 TEL: 786-985-6733
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. DEC. 22/ 2017
 ACTION: DENIED
  
 1) COMPLIED. A-2 JUICE BAR OCCUPANT LOAD OF 98.
  
 2) 2ND REVIEW TITLEBLOCK LIST THE TENANCY A JUICE BAR,
 SHEET A.1 DOES NOT HAVE A KITCHEN ALTHOUGH TWO OF THE 3
 SPACES FOR SERVICING JUICE ARE LABELED DINING ROOMS. IF
 THERE IS NO KITCHEN THE BUILDING OFFICIAL MR. BROWN
 OBJECTS TO THE TERM DINING ROOM, PLEASE LABEL THE ROOM
 THAT MOST DESCRIBES THE USE OF THE ROOM, JUICE BAR
 WOULD BE MORE ADEQUATE. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) THE MEETING THAT WAS HELD BETWEEN FRIEDERIKE
 MITTNER, VICTORIA AMADOR AND MYSELF ON 12/20/2017
 DISCUSSED THE REPLACEMENT OF DOORS WITH OUTSWING DOORS
 FRONT AND BACK WITH THE EXCEPTION OF THE 2 SIDE DOORS,
 TO BE FIXED IN PLACE, ADD SIGNAGE NOT A DOOR, AND THE
 CENTER DOOR AT THE FRONT BE THE EGRESS DOOR AND THE
 REAR DOOR BE THE 2ND MEANS OF EGRESS. BOTH SETS OF DOOR
 WILL NEED TO BE RECESSED BACK INTO THE SPACE AND SWING
 OUT. DEPENDING ON THE DESIGN OF THE FRONT DOOR IF THERE
 WILL BE 18 INCHES FOR MANEUVERING CLEARANCES OR IF AN
 ELECTRIC PUSH BUTTON AND AUTOMATIC AND POWER ASSISTED
 DOOR WITH BATTERY BACKUP WILL BE USED TO MEET THE
 REQUIREMENTS FOUND IN THE 2014 FBC-ACCESSIBILITY CODE
 404.2.4 MANEUVERING CLEARANCES OR 404.3 AUTOMATIC AND
 POWER ASSISTED DOORS.
  
 4) SEMI-COMPLIED. 93 SEATS X 0.05= 4.6 OR 5 ACCESSIBLE
 SEATS.
  
 5)SEMI-COMPLIED. 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES. THERE IS NO ACCESSIBLE SEATING ALONG
 THE WALL AT COUNTER NOR AT THE JUICE BAR.
  
 6) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, AND LUNCH COUNTERS.
  
 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 7) COMPLIED. SHEET A.3 INDICATES 2 NEW ACCESSIBLE
 RESTROOMS
  
 8)THIS REVIEW A SURVEY WAS SUBMITTED BOTH THE FRONT
 DOORS AND REAR DOORS WILL SWING OVER THE PROPERTY LINE,
 THEY WILL NEED TO BE RECESSED SO THE OUTSWING DOOR DOES
 NOT SWING OVER THE PROPERTY LINE SHOW COMPLIANCE WITH
 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET
 IN HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET IN HEIGHT SHALL BE PROHIBITED EXCEPT
 AS PROVIDED FOR IN SECTIONS 3202.2.1 THROUGH 3202.2.3.
 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE
 PUBLIC RIGHT-OF-WAY.
  
 9) SHEET D1 NOTE NUMBER 4 INDICATES PARTIALLY REMOVE
 EXISTING WALL TO ACCOMMODATE NEW WINDOWS AND/ OR DOORS
 OPENINGS. DO NOT REMOVE ANY STRUCTURAL BEAMS OR
 COLUMNS. NOTIFY ENGINEER IF CONFLICT EXIST. PLEASE NOTE
 THERE ARE NO STRUCTURAL SHEETS WITH THIS SET OF PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 10)SEMI-COMPLIED.2ND REVIEW. THE COVERSHEET LIST DESIGN
 PRESSURES AND THE WIND SPEED OF 161VULT AND 127 VASD.
 PLEASE CORRECT THE EASTERLY WIND DESIGN DELINEATION IS
 170 MPH, VULT. SEE 2014 FBC-B FIGURE 1609A FOR BUILDING
 RISK CATEGORY II NOT 160.
  
 2ND REVIEW. SHEET A.2. THE SUBMITTED DESIGN CRITERIA
 WAS BASED ON PRESSURES SHOWING A ROOF SLOPE BETWEEN 7
 DEGREES AND 27 DEGREES. THIS ROOF IS A FLAT ROOF
 PRESSURES WILL BE GREATER.
  
 1ST REVIEW. PLEASE NOTE THERE IS NO WIND DESIGN
 CRITERIA GIVEN, PLEASE PROVIDE THE FOLLOWING FOR CODE
 COMPLIANCE:
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 10.1. PROVIDED. ULTIMATE DESIGN WIND SPEED, VULT,
 (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 10.2. PROVIDED. RISK CATEGORY.
  
 10.3. SEMI PROVIDED, PROVIDE THE ROOF HEIGHT. WIND
 EXPOSURE. APPLICABLE WIND DIRECTION IF MORE THAN ONE
 WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. HEIGHT AND
 EXPOSURE.
  
 10.4.PROVIDED. APPLICABLE INTERNAL PRESSURE
 COEFFICIENT.
  
 10.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 11) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH THE
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 12) 2ND REQUEST. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 13) THE PLANS DO NOT INDICATE THE USE OR INSTALLATION
 OF WINDOW OR DOOR SUB-BUCKS. PLEASE PROVIDE SUB-BUCK
 DETAILS FOR WINDOW AND DOORS. PLEASE INCLUDE FASTENING
 OF BUCK TO THE SUBSTRATE BELOW. FBC-B 1710.10 MASONRY,
 CONCRETE OR OTHER STRUCTURAL SUBSTRATE. . UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED.
  
 14) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  