| 2018-01-04 11:53:05 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17101103 |
| | ADD: 538 NORTHWOOD RD. |
| | CONT: AUTHORIZED ADVANCED GENERAL CONTRACTORS INC. |
| | TEL: 786-985-6733 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. DEC. 22/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. A-2 JUICE BAR OCCUPANT LOAD OF 98. |
| | |
| | 2) 2ND REVIEW TITLEBLOCK LIST THE TENANCY A JUICE BAR, |
| | SHEET A.1 DOES NOT HAVE A KITCHEN ALTHOUGH TWO OF THE 3 |
| | SPACES FOR SERVICING JUICE ARE LABELED DINING ROOMS. IF |
| | THERE IS NO KITCHEN THE BUILDING OFFICIAL MR. BROWN |
| | OBJECTS TO THE TERM DINING ROOM, PLEASE LABEL THE ROOM |
| | THAT MOST DESCRIBES THE USE OF THE ROOM, JUICE BAR |
| | WOULD BE MORE ADEQUATE. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 3) THE MEETING THAT WAS HELD BETWEEN FRIEDERIKE |
| | MITTNER, VICTORIA AMADOR AND MYSELF ON 12/20/2017 |
| | DISCUSSED THE REPLACEMENT OF DOORS WITH OUTSWING DOORS |
| | FRONT AND BACK WITH THE EXCEPTION OF THE 2 SIDE DOORS, |
| | TO BE FIXED IN PLACE, ADD SIGNAGE NOT A DOOR, AND THE |
| | CENTER DOOR AT THE FRONT BE THE EGRESS DOOR AND THE |
| | REAR DOOR BE THE 2ND MEANS OF EGRESS. BOTH SETS OF DOOR |
| | WILL NEED TO BE RECESSED BACK INTO THE SPACE AND SWING |
| | OUT. DEPENDING ON THE DESIGN OF THE FRONT DOOR IF THERE |
| | WILL BE 18 INCHES FOR MANEUVERING CLEARANCES OR IF AN |
| | ELECTRIC PUSH BUTTON AND AUTOMATIC AND POWER ASSISTED |
| | DOOR WITH BATTERY BACKUP WILL BE USED TO MEET THE |
| | REQUIREMENTS FOUND IN THE 2014 FBC-ACCESSIBILITY CODE |
| | 404.2.4 MANEUVERING CLEARANCES OR 404.3 AUTOMATIC AND |
| | POWER ASSISTED DOORS. |
| | |
| | 4) SEMI-COMPLIED. 93 SEATS X 0.05= 4.6 OR 5 ACCESSIBLE |
| | SEATS. |
| | |
| | 5)SEMI-COMPLIED. 226.2 DISPERSION. DINING SURFACES AND |
| | WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE |
| | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING |
| | DINING SURFACES. THERE IS NO ACCESSIBLE SEATING ALONG |
| | THE WALL AT COUNTER NOR AT THE JUICE BAR. |
| | |
| | 6) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, AND LUNCH COUNTERS. |
| | |
| | 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 7) COMPLIED. SHEET A.3 INDICATES 2 NEW ACCESSIBLE |
| | RESTROOMS |
| | |
| | 8)THIS REVIEW A SURVEY WAS SUBMITTED BOTH THE FRONT |
| | DOORS AND REAR DOORS WILL SWING OVER THE PROPERTY LINE, |
| | THEY WILL NEED TO BE RECESSED SO THE OUTSWING DOOR DOES |
| | NOT SWING OVER THE PROPERTY LINE SHOW COMPLIANCE WITH |
| | FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET |
| | IN HEIGHT. |
| | ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE |
| | AND BELOW 8 FEET IN HEIGHT SHALL BE PROHIBITED EXCEPT |
| | AS PROVIDED FOR IN SECTIONS 3202.2.1 THROUGH 3202.2.3. |
| | DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE |
| | PUBLIC RIGHT-OF-WAY. |
| | |
| | 9) SHEET D1 NOTE NUMBER 4 INDICATES PARTIALLY REMOVE |
| | EXISTING WALL TO ACCOMMODATE NEW WINDOWS AND/ OR DOORS |
| | OPENINGS. DO NOT REMOVE ANY STRUCTURAL BEAMS OR |
| | COLUMNS. NOTIFY ENGINEER IF CONFLICT EXIST. PLEASE NOTE |
| | THERE ARE NO STRUCTURAL SHEETS WITH THIS SET OF PLANS. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 10)SEMI-COMPLIED.2ND REVIEW. THE COVERSHEET LIST DESIGN |
| | PRESSURES AND THE WIND SPEED OF 161VULT AND 127 VASD. |
| | PLEASE CORRECT THE EASTERLY WIND DESIGN DELINEATION IS |
| | 170 MPH, VULT. SEE 2014 FBC-B FIGURE 1609A FOR BUILDING |
| | RISK CATEGORY II NOT 160. |
| | |
| | 2ND REVIEW. SHEET A.2. THE SUBMITTED DESIGN CRITERIA |
| | WAS BASED ON PRESSURES SHOWING A ROOF SLOPE BETWEEN 7 |
| | DEGREES AND 27 DEGREES. THIS ROOF IS A FLAT ROOF |
| | PRESSURES WILL BE GREATER. |
| | |
| | 1ST REVIEW. PLEASE NOTE THERE IS NO WIND DESIGN |
| | CRITERIA GIVEN, PLEASE PROVIDE THE FOLLOWING FOR CODE |
| | COMPLIANCE: |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 10.1. PROVIDED. ULTIMATE DESIGN WIND SPEED, VULT, |
| | (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND |
| | SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 10.2. PROVIDED. RISK CATEGORY. |
| | |
| | 10.3. SEMI PROVIDED, PROVIDE THE ROOF HEIGHT. WIND |
| | EXPOSURE. APPLICABLE WIND DIRECTION IF MORE THAN ONE |
| | WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. HEIGHT AND |
| | EXPOSURE. |
| | |
| | 10.4.PROVIDED. APPLICABLE INTERNAL PRESSURE |
| | COEFFICIENT. |
| | |
| | 10.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 11) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH THE |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 12) 2ND REQUEST. PLEASE IDENTIFY ON THE PRODUCT |
| | APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL |
| | PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING |
| | WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF |
| | REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH |
| | OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. |
| | WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND |
| | SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| | SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| | USED IN THE TESTS. |
| | |
| | 13) THE PLANS DO NOT INDICATE THE USE OR INSTALLATION |
| | OF WINDOW OR DOOR SUB-BUCKS. PLEASE PROVIDE SUB-BUCK |
| | DETAILS FOR WINDOW AND DOORS. PLEASE INCLUDE FASTENING |
| | OF BUCK TO THE SUBSTRATE BELOW. FBC-B 1710.10 MASONRY, |
| | CONCRETE OR OTHER STRUCTURAL SUBSTRATE. . UNLESS |
| | OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE |
| | INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS PROVIDED. |
| | |
| | 14) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |