2017-11-07 17:45:491ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17101103
 11/7/17
  
 PLAN REVIEW RESULTS: DENIED.
 PLEASE ADDRESS THE FOLLOWING COMMENTS.
  
 1) SHEET CV-1: REFER TO BUILDING REVIEW COMMENTS AND
 ADDRESS THE DISCREPANCIES IN THE BUILDING CODE AND
 DESIGN DATA. A THOROUGH MECHANICAL REVIEW CANNOT BE
 COMPLETED UNTIL THE CORRECT OCCUPANCY CLASIFICATIONS
 ARE ESTABLISHED. BASED ON THE BUILDING PLAN REVIEWER'S
 RESEARCH THE PROPOSED TENANT BUILDOUT APPEARS TO BE A
 CHANGE OF OCCUPANCY AND SHALL BE IN COMPLIANCE
  
 WITH SECTION C101.4.4 FBC-14 ENERGY CONSERVATION CODE.
 REFER TO SECTIONS C101.5 AND C401.2 AND SUBMIT AN
 ENERGY COMPLIANCE REPORT.
  
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE THAT
 AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS ARE REQUIRED
 FOR THE O/A INTAKE DUCTS- SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION.
  
 3) SHEET H.1: THE SCHEDULE INDICATES EACH OF THE THREE
 4-TON SYSTEMS WILL PRODUCE 1600 CFMS OF AIR HOWEVER THE
 PLANS SHOW EACH SYSTEM SUPPLYING ONLY 700 CFMS
 APPROXIMATELY TO EACH OF THE THREE GALLERIES- PLEASE
 CLARIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  