Plan Review Notes
Plan Review Notes For Permit 17101103
Permit Number 17101103
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-10-30 13:16:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 3 - THERE IS AN EXIT OPENING INDICATED IN
 THE REAR, CENTER AREA. THERE ARE NO DIMENSIONS
 INDICATED FOR THIS OPENING.
  
 PLEASE PROVIDE AND ENSURE IT MEETS THE MINIMUM
 REQUIREMENTS PER NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 7.3.4 MINIMUM WIDTH.
 7.3.4.1 THE WIDTH OF ANY MEANS OF EGRESS, UNLESS
 OTHERWISE
 PROVIDED IN 7.3.4.1.1 THROUGH 7.3.4.1.3, SHALL BE AS
 FOLLOWS:
 (1) NOT LESS THAN THAT REQUIRED FOR A GIVEN EGRESS
 COMPONENT IN
 THIS CHAPTER OR CHAPTERS 11 THROUGH 43
 (2) NOT LESS THAN 36 IN. (915 MM) WHERE ANOTHER PART OF
 THIS
 CHAPTER AND CHAPTERS 11 THROUGH 43 DO NOT SPECIFY A
 MINIMUM WIDTH
  
  
  
  
  
 2) SHEET A 3 - THERE IS A SET OF DOUBLE DOORS INDICATED
 AS AN EXIT IN THE REAR AREA. THESE DOORS SWING INWARD
 TOWARDS THE PATH OF EGRESS. THESE DOORS ARE REQUIRED TO
 SWING IN THE PATH OF EGRESS. THIS DOOR DOES NOT HAVE
 PANIC HARDWARE INDICATED FOR IT. SEE # 6 BELOW.
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION OF
 EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY
 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE
 DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS DIRECTLY
 INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
  
  
 3) SHEET A 3 - THE DOUBLE DOORS IN THE REAR AREA ARE
 INDICATED AS AN EXIT LEADING INTO AN OFFICE AREA, THEN
 THRU ANOTHER DOOR INTO A VESTIBULE. THIS EXIT SHALL NOT
 PASS THRU AN OFFICE.
  
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR SIMILAR
 SPACES, OR
 OTHER ROOMS OR SPACES SUBJECT TO LOCKING, UNLESS
 PASSAGE THROUGH
 SUCH ROOMS OR SPACES IS PERMITTED FOR THE OCCUPANCY BY
 CHAPTER
 18, 19, 22, OR 23.
  
 12.2.5.2 ACCESS THROUGH HAZARDOUS AREAS. MEANS OF
 EGRESS
 FROM A ROOM OR SPACE FOR ASSEMBLY PURPOSES SHALL NOT BE
 PERMITTED THROUGH KITCHENS, STOREROOMS, RESTROOMS,
 CLOSETS,
 PLATFORMS, STAGES, PROJECTION ROOMS, OR HAZARDOUS AREAS
 AS
 DESCRIBED IN 12.3.2.
  
  
  
  
 4) SHEET A 3 - SHOULD THE EXITING THRU THE SPACE
 INDICATED IN # 3 ABOVE, BE LATER APPROVED THRU
 REVISIONS, THE DOOR LEADING OUT OF THE OFFICE IS NOT
 INDICATED WITH A EXIT SIGN.
  
 PLEASE PROVIDE AN EXIT SIGN IF THIS CAN BE APPROVED TRU
 REVISIONS.
  
  
  
 5) SHEET A 3 - THERE IS A DOUBLE DOOR EXIT INDICATED AT
 THE REAR OF THE BUILDING. IT IS NOT CLEAR THAT THIS
 EXIT LEADS TO A PUBLIC WAY. PLEASE PROVIDE SITE PALN
 DETAILS SHOWING COMPLIANCE WITH THE CODE.
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A
 PUBLIC WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS
 OTHERWISE
 PROVIDED IN 7.7.1.2 THROUGH 7.7.1.4.
 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS
 OF THE EXIT
 DISCHARGE SHALL BE OF THE REQUIRED WIDTH AND SIZE TO
 PROVIDE ALL
 OCCUPANTS WITH A SAFE ACCESS TO A PUBLIC WAY.
  
  
  
  
 6) SHEET A 3 & D 1 - THERE IS NO INDICATION OF A DOOR
 SCHEDULE. PLEASE PROVIDE ALL APPLICABLE DOOR
 INFORMATION ON A DOOR SCHEULDE INCLUDING ALL LOCKING
 DEVICES AND ENSURE THEY MEET THE REQUIRERMENTS OF THE
 CODE.
  
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR
 LOCK IS PANIC HARDWARE OR FIRE EXIT HARDWARE COMPLYING
 WITH
 7.2.1.7, UNLESS OTHERWISE PERMITTED BY ONE OF THE
 FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED
 EGRESS DOORS AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE
 PERMITTED TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR
 OF DOORS IF
 BOTH OF THE FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE
 ASSEMBLY OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER
 THAN
 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL