 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE IS A PROPOSED ELECTRICAL PLAN ON SHEET E.1 AND
 ONE ON SHEET E.2 THAT ARE DIFFERENT. CLARIFY AND/OR
 CORRECT. FBC 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. ALL LIGHTING SHOULD BE FIGURED AT 125% FOR
 CONTINUOUS LOAD. MAKE SURE MATH IS CORRECT, THERE ARE 3
 PHASE CALCULATIONS ON PANEL SCHEDULES AND SINGLE PHASE
 CALCULATIONS ON LOAD CALC. TOTAL CONNECTED LOAD DOES
 NOT MATCH WHAT IS STATED IN PANEL SCHEDULE. NEC 220
 3. WHY ARE THERE 2 PANEL SCHEDULES FOR EACH PANEL?
 REMOVE CONFLICTING OR REDUNDANT INFORMATION. FBC
 107.2.1
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. A CONFLICT EXIST BETWEEN THE STATED AIC RATING OF
 PANELS ON THE RISER DIAGRAM AND WHAT IS STATED ON PANEL
 SCHEDULES. PROVIDE CORRECTION. NEC 110.9; FBC 107.2.1
 6. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5
 7. PROVIDE LIGHT FIXTURE SCHEDULE. NEC 110.3
 8. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2
 9. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC CE 405.2.4
 10. PROVIDE SHOW WINDOW OUTLETS AND CIRCUIT PER CODE.
 NEC 210.62
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  