| 2017-11-14 15:42:11 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THERE IS A PROPOSED ELECTRICAL PLAN ON SHEET E.1 AND |
| | ONE ON SHEET E.2 THAT ARE DIFFERENT. CLARIFY AND/OR |
| | CORRECT. FBC 107.2.1 |
| | 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. ALL LIGHTING SHOULD BE FIGURED AT 125% FOR |
| | CONTINUOUS LOAD. MAKE SURE MATH IS CORRECT, THERE ARE 3 |
| | PHASE CALCULATIONS ON PANEL SCHEDULES AND SINGLE PHASE |
| | CALCULATIONS ON LOAD CALC. TOTAL CONNECTED LOAD DOES |
| | NOT MATCH WHAT IS STATED IN PANEL SCHEDULE. NEC 220 |
| | 3. WHY ARE THERE 2 PANEL SCHEDULES FOR EACH PANEL? |
| | REMOVE CONFLICTING OR REDUNDANT INFORMATION. FBC |
| | 107.2.1 |
| | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 5. A CONFLICT EXIST BETWEEN THE STATED AIC RATING OF |
| | PANELS ON THE RISER DIAGRAM AND WHAT IS STATED ON PANEL |
| | SCHEDULES. PROVIDE CORRECTION. NEC 110.9; FBC 107.2.1 |
| | 6. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| | ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| | CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| | CODE. FBC CE 405.5 |
| | 7. PROVIDE LIGHT FIXTURE SCHEDULE. NEC 110.3 |
| | 8. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2, |
| | 405.2.2.2 |
| | 9. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC |
| | 600.5; FBC CE 405.2.4 |
| | 10. PROVIDE SHOW WINDOW OUTLETS AND CIRCUIT PER CODE. |
| | NEC 210.62 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |