Plan Review Notes
Plan Review Notes For Permit 17101103
Permit Number 17101103
Review Stop B
Sequence Number 1
Notes
Date Text
2017-11-01 07:26:452014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17101103
 ADD: 538 NORTHWOOD RD.
 CONT: AUTHORIZED ADVANCED GENERAL CONTRACTORS INC.
 TEL: 786-985-6733
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 31/ 2017
 ACTION: DENIED
  
 1) THE COVER SHEET CV.1 INDICATES A GROSS SQ. FT. OF
 2920. THE OCCUPANCY TYPE AS A3 WITH A GALLERY, JUICE
 BAR AND LOUNGE AREA AND A 3RD AREA LABELED A WELLNESS
 STUDIO. THE COVERSHEET ALSO INDICATES 1916 SQ. FT. IS
 DEDICATED TO DINING WHICH TRANSLATES INTO 127.33 OR 128
 OCCUPANTS. PLEASE NOTE DINING AND THE CONSUMPTION OF
 DRINK IS CLASSIFIED AS AN A2 OCCUPANCY. PLEASE UPDATE
 PLANS. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) THE OTHER ISSUE IS THE CHANGE OF OCCUPANCY HAS NOT
 BEEN DECLARED. THE LAST USE FOR THIS TENANT SPACE WAS
 CONSIGNMENT SHOP WHICH IS CONSIDERED A MERCANTILE
 OCCUPANCY. IT WOULD APPEAR THIS IS TO BE A MIXED USE
 BETWEEN A A-2 ESTABLISHMENT AND POSSIBLY A BUSINESS
 OCCUPANCY, THE BUSINESS OCCUPANCY BEING THE WELLNESS
 STUDIO. PLEASE EXPLAIN WHAT THE FUNCTION OF THIS AREA
 WILL BE SINCE IT STILL LOOKS LIKE PART OF THE
 RESTAURANT. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3A) WITH THE COVERSHEET LISTING AN OCCUPANT LOAD OF 128
 FOR AN ESTABLISHMENT THAT SERVES EITHER FOOD OR DRINK
 ,THIS WILL CREATE AN A-2 OCCUPANCY AND A CHANGE OF
 OCCUPANCY. THE 2014 EXISTING BUILDING CODE
 SECTION 1001.3.1. PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 1012 SHALL APPLY.
  
 1012.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION. WHERE A PORTION OF AN EXISTING BUILDING IS
 CHANGED TO A NEW OCCUPANCY CLASSIFICATION AND THAT
 PORTION IS NOT SEPARATED FROM THE REMAINDER OF THE
 BUILDING WITH FIRE BARRIERS HAVING A FIRE-RESISTANCE
 RATING AS REQUIRED IN THE FLORIDA BUILDING CODE,
 BUILDING FOR THE SEPARATE OCCUPANCY, THE ENTIRE
 BUILDING SHALL COMPLY WITH ALL OF THE REQUIREMENTS OF
 CHAPTER 9 APPLIED THROUGHOUT THE BUILDING FOR THE MOST
 RESTRICTIVE OCCUPANCY CLASSIFICATION IN THE BUILDING
 AND WITH THE REQUIREMENTS OF THIS CHAPTER.
  
 1012.2 FIRE PROTECTION SYSTEMS. FIRE PROTECTION SYSTEMS
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS 1012.2.1
 AND 1012.2.2.
  
 1012.2.1 FIRE SPRINKLER SYSTEM. WHERE A CHANGE IN
 OCCUPANCY CLASSIFICATION OCCURS THAT REQUIRES AN
 AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED ON
 THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE
 FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL BE
 PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS.
 2014 FBC-B SECTION 903.2.1.2 GROUP A-2. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2
 OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS:
 (2.) THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE.
  
 3B) SHEET A.3 INDICATES A2 RESTAURANT OCCUPANCY WITH A
 BUSINESS OCCUPANCY (WELLNESS STUDIO) WHICH WILL BE
 CONSIDERED A MIXED USE OCCUPANCY. PLEASE PROVIDE HOW
 OCCUPANCY SEPARATION WILL BE MAINTAINED REQUIRED BY THE
 2014 FBC-B TABLE 508.4, 1 HOUR WITH FIRE SPRINKLERS AND
 2 HOURS FOR NON-SPRINKLERED TENANT SPACES.
  
 3C) THE EXTERIOR SIDE WALL OF THE GALLERY PLEASE ALSO
 PROVIDE THE FIRE RATING FOR THIS WALL. SEE FBC-B TABLE
 602.
  
 4) THE COVERSHEET INDICATES 115 CHAIRS AT TABLES, THERE
 IS ALSO A CALCULATION OF DINING FLOOR AREA OF 1916 SQ.
 FT./ 15 = 128 OCCUPANTS. 128 X 0.05 = 6.4 OR 7 REQUIRED
 ACCESSIBLE CHAIRS AT VARIOUS LOCATIONS. PLEASE
 SHOW COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE
 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 5) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 6) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ABA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 7) SHEET A.3 INDICATES 2 NEW ACCESSIBLE RESTROOMS, BUT
 THERE IS NO DETAILS SHOWING FIXTURE DISTANCES FROM
 WALLS, GRAB BARS, AND RESTROOM ACCESSORIES.
  
 8) PLEASE PROVIDE A SURVEY OF THE PROPERTY SHOWING THE
 PROPERTY LINES. SHEET D1 THE DEMO PLAN SHOWS THE
 REMOVAL OF ALL STOREFRONT WINDOWS AND DOORS. THIS SAME
 SHEET SHOWS ALL OF THE STOREFRONT DOORS AS INSWING
 DOORS, THE BACK EGRESS DOOR OUTSWING DOORS. SHEET A.3
 SHOWS ALL OF THE STOREFRONT DOORS AND THE REAR DOOR AS
 OUTSWING DOORS. PLEASE PROVIDE A SURVEY TO SHOW
 COMPLIANCE WITH FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE
 AND BELOW 8 FEET IN HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET IN HEIGHT SHALL BE PROHIBITED EXCEPT
 AS PROVIDED FOR IN SECTIONS 3202.2.1 THROUGH 3202.2.3.
 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE
 PUBLIC RIGHT-OF-WAY.
  
 9) SHEET D1 NOTE NUMBER 4 INDICATES PARTIALLY REMOVE
 EXISTING WALL TO ACCOMMODATE NEW WINDOWS AND/ OR DOORS
 OPENINGS. DO NOT REMOVE ANY STRUCTURAL BEAMS OR
 COLUMNS. NOTIFY ENGINEER IF CONFLICT EXIST. PLEASE NOTE
 THERE ARE NO STRUCTURAL SHEETS WITH THIS SET OF PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) PLEASE NOTE THERE IS NO WIND DESIGN CRITERIA GIVEN,
 PLEASE PROVIDE THE FOLLOWING FOR CODE COMPLIANCE:
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 10.1. PROVIDED. ULTIMATE DESIGN WIND SPEED, VULT,
 (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 10.2. PROVIDED. RISK CATEGORY.
  
 10.3. SEMI PROVIDED, PROVIDE THE ROOF HEIGHT. WIND
 EXPOSURE. APPLICABLE WIND DIRECTION IF MORE THAN ONE
 WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. HEIGHT AND
 EXPOSURE.
  
 10.4.PROVIDED. APPLICABLE INTERNAL PRESSURE
 COEFFICIENT.
  
 10.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 11) PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 12) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 13) THE PLANS DO NOT INDICATE THE USE OR INSTALLATION
 OF WINDOW OR DOOR SUB-BUCKS. PLEASE PROVIDE SUB-BUCK
 DETAILS FOR WINDOW AND DOORS. PLEASE INCLUDE FASTENING
 OF BUCK TO THE SUBSTRATE BELOW. FBC-B 1710.10 MASONRY,
 CONCRETE OR OTHER STRUCTURAL SUBSTRATE. . UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED.
  
 14) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  