| Date |
Text |
| 2017-11-27 08:58:40 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S INSTALLATION |
| | MANUAL FOR THE TANKLESS WATER HEATERS. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 2) SHOW THE DISTANCE OF THE TANKLESS WATER HEATERS FROM |
| | ALL OPERABLE WINDOWS AND DOORS. THE LOCATION SHALL |
| | COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. |
| | 3) SHT. A-4 - SHOW THE FIXTURE CLEARANCES OF THE |
| | LAVATORY AND WATER CCLOSET IN THE MAIN HOUSE AND ALSO |
| | IN THE STORAGE SHAED. FIXTURE CLEARANCES SHALL COMPLY |
| | WITH THE 2014 FBC-RESIDENTIAL SEC.P2705.1. |
| | 4) SHOW THE SHOWER LENGTH AND WIDTH DIMENSIONS ON THE |
| | FLOOR PLAN FOR THE SHOWER IN THE STORAGE SHED. COMPLY |
| | WITH 2014 FBC-RES. SEC. P 2708.1. |
| | 5) THE PLANS SHOW THE ENTIRE WATER SYSTEM CONNECTED TO |
| | AN EXISTINF 1/2 INCH WATER SERVICE. THE WATER SYSTEM |
| | SHALL BE SIZED TO PROVIDE THE CAPACITIES AND PRESSURES |
| | TO THE POINT OF OUTLET DISCHARGE IN ACCORDANCE WITH |
| | 2015 FBC RESIDENTIAL SECS. P2903.1, P2903.3 AND TABLE |
| | P2903.1. |
| | 6) THE MINIMUM SIZE OF THE WATER SERVICE PIPE TO THE |
| | STRUCTURE AND TO THE STORAGE SHED SHALL BE 3/4 INCH PER |
| | THE 2014 FBC-RES. SEC. P2903.7. |
| | 7) INDICATE ON THE PLANS IF THE FIREPLACE IS WOOD OR |
| | GAS BURNING. IF GAS, THIS LOAD SHALL BE ADDED INTO THE |
| | SIZING OF THE GAS SYSTEM FOR THE TANKLESS WATER |
| | HEATERS. |
| | 8) SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| | GAS SYSTEM. WPB AMEND. TO FBC SEC. 107.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |