| Plan Review Notes For Permit 17101099 |
| Permit Number |
17101099 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-27 14:51:27 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | PERMIT #17101099 | | | 11/27/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1: THE AC EQUIPMENT SCHEDULE INDICATES THE | | | 24000 BTUH (2-TON) AC SYSTEM WILL PRODUCE 6000 CFMS- | | | PLEASE CORRECT. THE AVERAGE 2-TON SYSTEM PRODUCES | | | APPROXIMATELY 800 CFMS. PLEASE NOTE THAT THE AC LAYOUT | | | PLAN IS INDICATING 1150 TOTAL SUPPLY CFMS WHICH ALSO | | | EXCEEDS THE CAPACITY OF THE SYSTEM, | | | | | | 2) PROVIDE CONDENSER TIE-DOWN DETAILS PER SECTIONS | | | M1305.1.4.1 AND M1401.4. | | | | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE RANGE | | | HOOD- SEE SECTION M1503.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|