| 2017-11-20 15:20:03 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ALL RECEPTACLES IN SHED ARE REQUIRED TO BE GFCI |
| | PROTECTED. PROVIDE CORRECTION. NEC 210.8; FBC RE 3902.2 |
| | 2. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER AT THE PANEL FOR PANEL 3. NEC 225.31, |
| | 225.32 |
| | 3. PROVIDE GROUNDING ELECTRODE SYSTEM AT SHED AS |
| | REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED BY A |
| | FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3 |
| | 4. PROVIDE ONE LOAD CALCULATION FOR ENTIRE SERVICE WITH |
| | ALL LOADS INCLUDED TO DETERMINE THAT THE SERVICE IS |
| | ADEQUATE. A SEPARATE LOAD CALCULATION FOR PANEL 2 IS |
| | PERMITTED FOR THE WIRE SIZE OF THE FEEDER TO THIS |
| | PANEL, HOWEVER, THE SAME TYPE OF CALCULATION IS NOT |
| | PERMITTED FOR PANEL 3. DEMAND FACTORS MAY ONLY BE USED |
| | WHEN THE FEEDER TO A PANEL IS 100 AMPS OR GREATER. |
| | PROVIDE FULL LOAD FOR PANEL 3 AND SIZE THE FEEDER WIRE |
| | AND OVERCURRENT PROTECTION ACCORDINGLY. FBC RE 3602.2; |
| | NEC 220.82(A) |
| | 5. A CONFLICT EXIST IN THE NOTES ON PLAN. SEVERAL AREAS |
| | STATE THAT THE 2011 NEC SHOULD BE USED, BUT NOTE 5 |
| | STATES THAT THE 2014 NEC SHOULD BE USED, WHICH IS NOT |
| | THE CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE |
| | 6. SMOKE AND CO ALARMS SHOULD BE INSTALLED AT LEAST 3 |
| | FEET FROM CEILING FANS OR MECHANICAL GRILLS. PROVIDE |
| | CORRECTION. NFPA 72, 29.8.3.6 AND .7. |
| | 7. DINING ROOM CIRCUIT IS SHOWN FEEDING THE WALL |
| | OUTLETS AND LIGHTING WITH THE SAME CIRCUIT. DINING ROOM |
| | WALL OUTLETS CANNOT BE FED FROM A LIGHTING CIRCUIT. |
| | PROVIDE CORRECTION. NEC 210.52(B)(2); FBC RE 3703.2 |
| | 8. PANEL SCHEDULE FOR PANEL 2 SHOWS CIRCUIT 1 AS A # 12 |
| | WIRE ON A 25 AMP BREAKER; CIRCUIT 19,21 AS A # 12 WIRE |
| | ON A 60 AMP BREAKER; CIRCUIT 8 AS A # 14 WIRE ON A 20 |
| | AMP BREAKER. PROVIDE CORRECT WIRE AND/OR BREAKER SIZES |
| | FOR THE AMPACITY OF THE WIRE. NEC 310.15(B)(16); FBC RE |
| | 3705.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |