| Plan Review Notes For Permit 17101099 |
| Permit Number |
17101099 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-12-02 10:14:43 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PRODUCT APPROVAL AFFIDAVIT LIST'S FLO10456-R3, | | | FL10446.8 & FL11473-R3. THESE PRODUCT APPROVALS ARE | | | MISSING FROM SUBMITTAL. | | | 2. ENERGY SUBMITTAL REQUIRES R38 TO BE INSTALLED IN | | | ATTIC. PLAN PAGE S2 SHOWS R19. PLEASE CORRECT PLAN | | | PAGE. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW, AND DOOR SUBMITTALS. | | | | | | R402.1 GENERAL (PRESCRIPTIVE). | | | THE BUILDING THERMAL ENVELOPE SHALL MEET THE | | | REQUIREMENTS OF SECTIONS R402.1.1 THROUGH R402.1.4. | | | |
|