2018-02-20 19:00:30ROOFING MATERIAL: POLYGLASS MODIFIED BITUMEN FL1654-20
  
 THE RAS117 CALCULATIONS ARE NOT ACCEPTABLE FOR THE
 FOLLOWING REASONS:
 1) THIS PRODUCT APPROVAL IS NOT A MIAMI-DADE NOTICE OF
 ACCEPTANCE. THIS IS A FLORIDA (DBPR) PRODUCT APPROVAL.
 IN ORDER TO AVOID CONFUSION, REMOVE THE NOA FROM THE FL
 1654-R20 FROM THE ENGINEER'S LETTER. FBC 107.2.1
  
 2) THE PAGE NUMBER FROM THE FLORIDA PRODUCT APPROVAL IS
 INCORRECTLY SPECIFIED AS SHEET 17 OF 58. THE SYSTEM
 NUMBER IS SPECIFIED ON THE ENGINEER'S LETTER AS W-94,
 WHICH IS LOCATED ON PAGE 18 OF 55. FBC 107.2.1
  
 3) THE REQUIRED UPLIFT PRESSURES FOR THE ROOF ZONES IS
 NOT SPECIFIED ON THE ENGINEER'S LETTER. THE WIND SPEED,
 EXPOSURE CATEGORY AND MEAN ROOF HEIGHT ARE ALSO NOT
 PROVIDED. FBC-R301.2.1
  
 4) THE W-94 ROOFING SYSTEM HAS A MAXIMUM DESIGN
 PRESSURE OF -67.5 PSF. THE LETTER STATES THAT THE
 MAXIMUM DESIGN PRESSURE IS -60 PSF. FBC 107.2.1
  
 5) THE W-94 ROOFING SYSTEM IS A PROPRIETARY SYSTEM AND
 REQUIRES POLYGLASS APP BASE FOR THE BASE SHEET. THE
 OTHERS LISTED IN THE LETTER CAN NOT BE USED WITH THIS
 SYSTEM. FBC 107.2.1
  
 6) THIS SYSTEM REQUIRES FOUR (4) EQUALLY SPACED
 STAGGERED CENTER ROWS AND THE LETTER ONLY SPECIFIES
 THREE (3). FBC 107.2.1
  
 7) THE PERIMETER AND CORNER AREA FASTENING DOES NOT
 SPECIFY THE LAP OR THE NUMBER OF CENTER ROWS. FBC
 107.2.1
  
 8) SUBMIT TWO SETS OF THE ACTUAL RAS 117 CALCULATIONS
 THAT WERE USED TO DETERMINE THE ENHANCED FASTENING. FBC
 107.2.1.3