2018-02-01 18:24:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 FBC 107.2.1
 THE RAS 117 CALCULATIONS ARE NOT ACCEPTABLE FOR THE
 FOLLOWING REASONS:
 1) THE SYSTEM NUMBER FROM THE FLORIDA PRODUCT APPROVAL
 (FL1654-R20) IS NOT SPECIFIED.
 2) THE PAGE NUMBER FROM THE FLORIDA PRODUCT APPROVAL IS
 NOT SPECIFIED.
 3) THE UPLIFT PRESSURE FOR ROOF ZONE 3 IS NOT CORRECT.
 IT SHOULD BE -95.7 PSF FOR THIS PROJECT.
 4) I COULD NOT FIND ANY SYSTEMS THAT HAVE A MAXIMUM
 DESIGN PRESSURE OF -60 PSF WITH FASTENER SPACINGS OF
 10"OC AT THE 4" LAP AND 6"OC IN THREE EQUALLY SPACED
 STAGGERED ROWS.