2018-02-01 18:32:12ROOFING MATERIAL: POLYGLASS MODIFIED BITUMEN FL1654-20
  
 THE RAS117 CALCULATIONS ARE NOT ACCEPTABLE FOR THE
 FOLLOWING REASONS:
 1) THE SYSTEM NUMBER FROM THE FLORIDA PRODUCT APPROVAL
 (FL1654-R20) IS NOT SPECIFIED.
 2) THE PAGE NUMBER FROM THE FLORIDA PRODUCT APPROVAL IS
 NOT SPECIFIED.
 3) THE UPLIFT PRESSURE FOR ROOF ZONE 3 IS NOT CORRECT.
 IT SHOULD BE -95.7 PSF FOR THIS PROJECT.
 4) I COULD NOT FIND ANY SYSTEMS THAT HAVE A MAXIMUM
 DESIGN PRESSURE OF -60 PSF WITH FASTENER SPACINGS OF
 10"OC AT THE 4" LAP AND 6"OC IN THREE EQUALLY SPACED
 STAGGERED ROWS.