| Plan Review Notes For Permit 17101066 |
| Permit Number |
17101066 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-01 18:32:12 | ROOFING MATERIAL: POLYGLASS MODIFIED BITUMEN FL1654-20 | | | | | | THE RAS117 CALCULATIONS ARE NOT ACCEPTABLE FOR THE | | | FOLLOWING REASONS: | | | 1) THE SYSTEM NUMBER FROM THE FLORIDA PRODUCT APPROVAL | | | (FL1654-R20) IS NOT SPECIFIED. | | | 2) THE PAGE NUMBER FROM THE FLORIDA PRODUCT APPROVAL IS | | | NOT SPECIFIED. | | | 3) THE UPLIFT PRESSURE FOR ROOF ZONE 3 IS NOT CORRECT. | | | IT SHOULD BE -95.7 PSF FOR THIS PROJECT. | | | 4) I COULD NOT FIND ANY SYSTEMS THAT HAVE A MAXIMUM | | | DESIGN PRESSURE OF -60 PSF WITH FASTENER SPACINGS OF | | | 10"OC AT THE 4" LAP AND 6"OC IN THREE EQUALLY SPACED | | | STAGGERED ROWS. |
|