2017-11-02 17:58:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ENERGY FORM R402 - 2014 IS REQUIRED TO BE SIGNED AND
 DATED BY THE PREPARER AND THE OWNER/AGENT CERTIFYING
 COMPLIANCE WITH THE ENERGY CODE. FBC ENERGY
 CONSERVATION SECTION R103.
  
 2) INDICATE THE SYSTEM NUMBER AND MAXIMUM DESIGN
 PRESSURE FOR THE ROOF COVERING THAT WILL BE USED ON THE
 PRODUCT APPROVAL FOR THE POLYGLASS MODIFIED BITUMEN
 ROOF SYSTEM. FBC 107.2.1
  
 3) SUBMIT TWO SETS OF SIGNED AND SEALED ENHANCED
 FASTENING CALCULATIONS FROM A FLORIDA LICENSED ENGINEER
 FOR THE POLYGLASS MODIFIED BITUMEN ROOF SYSTEM. SEE
 NOTE 8 ON PAGE 2 OF 55 OF THE PRODUCT APPROVAL. FBC -
 R301.2.1
  
  