| Notes |
| Date |
Text |
| 2017-11-02 17:58:04 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ENERGY FORM R402 - 2014 IS REQUIRED TO BE SIGNED AND | | | DATED BY THE PREPARER AND THE OWNER/AGENT CERTIFYING | | | COMPLIANCE WITH THE ENERGY CODE. FBC ENERGY | | | CONSERVATION SECTION R103. | | | | | | 2) INDICATE THE SYSTEM NUMBER AND MAXIMUM DESIGN | | | PRESSURE FOR THE ROOF COVERING THAT WILL BE USED ON THE | | | PRODUCT APPROVAL FOR THE POLYGLASS MODIFIED BITUMEN | | | ROOF SYSTEM. FBC 107.2.1 | | | | | | 3) SUBMIT TWO SETS OF SIGNED AND SEALED ENHANCED | | | FASTENING CALCULATIONS FROM A FLORIDA LICENSED ENGINEER | | | FOR THE POLYGLASS MODIFIED BITUMEN ROOF SYSTEM. SEE | | | NOTE 8 ON PAGE 2 OF 55 OF THE PRODUCT APPROVAL. FBC - | | | R301.2.1 | | | | | | |
|