2017-10-30 13:35:07BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVAL FOR PROPOSED OVERHEAD
 DOORS.
 2. SUBMITTED PLAN SHOWS THE REMOVAL OF ONE SET OF
 STAIRS. PROVIDE LIFE SAFETY PLAN TO DEMONSTRATE
 COMPLIANCE WITH FBC CHPT. 10 MEANS OF EGRESS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE OVERHEAD DOOR SUBMITTALS.
  
 MEANS OF EGRESS
  
 1001.1 GENERAL.
 BUILDINGS OR PORTIONS THEREOF SHALL BE PROVIDED WITH A
 MEANS OF EGRESS SYSTEM AS REQUIRED BY THIS CHAPTER. THE
 PROVISIONS OF THIS CHAPTER SHALL CONTROL THE DESIGN,
 CONSTRUCTION AND ARRANGEMENT OF MEANS OF EGRESS
 COMPONENTS REQUIRED TO PROVIDE AN APPROVED MEANS OF
 EGRESS FROM STRUCTURES AND PORTIONS THEREOF.
  
 1001.2 MINIMUM REQUIREMENTS.
 IT SHALL BE UNLAWFUL TO ALTER A BUILDING OR STRUCTURE
 IN A MANNER THAT WILL REDUCE THE NUMBER OF EXITS OR THE
 CAPACITY OF THE MEANS OF EGRESS TO LESS THAN REQUIRED
 BY THIS CODE.
  
  
  