| Plan Review Notes For Permit 17100958 |
| Permit Number |
17100958 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-26 12:34:31 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS INSUFFICIENT DETAIL PROVIDED TO CONDUCT AN | | | ADAQUATE PLAN REVIEW. | | | | | | | | | 2) THE SUBMITTED PLAN DOES NOT INDICATE WHAT IS AN | | | EXISTING, RELOCATED, NEW OR REMOVED SPRINKLER HEAD. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 3) THE SUBMITTED PLANS DO NOT INDICATE WHAT IS AND WHAT | | | SIZE IS AN EXISTING, RELOCATED, NEW OR REMOVED BRANCH | | | LINE PIPING. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 4) SIDEWALL SPRINKLERS ARE INDICATED, ARE THESE | | | EXISTING AND/OR ARE THERE ANY OBSTRUCTIONS, INCLUDING | | | BUT NOT LIMITED TO, CEILING FANS AND/OR LIGHT FIXTURES | | | IN THESE ROOMS OR AREAS? | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 5) BASED ON ANY OF THE ABOVE, PLEASE INDICATE IF THE | | | EXISITNG HYDRALIC CALCULATIONS WILL BE AFFECTED AND IF | | | SO, PROVIDE REVISED CALCULATIONS. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|