| Plan Review Notes For Permit 17100922 |
| Permit Number |
17100922 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-30 14:20:10 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | SOME OF THE PAGES DO NOT PERTAIN TO THE SIGN? | | | | | | NEED TO SHOW DISCONNECTS REQUIRED BY CODE 600.6 | | | | | | CONTROL OF THE SIGN FOR ENERGY CODE | | | C405.2.4 EXTERIOR LIGHTING CONTROLS. | | | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN | | | OPERATION SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME | | | SWITCH OR PHOTOSENSOR. ALL TIME SWITCHES SHALL BE | | | CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING | | | DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. | | | |
|