Plan Review Notes
Plan Review Notes For Permit 17100922
Permit Number 17100922
Review Stop E
Sequence Number 1
Notes
Date Text
2017-10-30 14:20:10FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SOME OF THE PAGES DO NOT PERTAIN TO THE SIGN?
  
 NEED TO SHOW DISCONNECTS REQUIRED BY CODE 600.6
  
 CONTROL OF THE SIGN FOR ENERGY CODE
 C405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN
 OPERATION SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME
 SWITCH OR PHOTOSENSOR. ALL TIME SWITCHES SHALL BE
 CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING
 DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  