| Date |
Text |
| 2017-10-31 04:58:14 | 1) SHT. C 103 - IDENTIFY IN THE NARRATIVE THE SPECIFIC |
| | CHANGES THAT HAVE BEEN MADE TO THIS DRAWING. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 2) IRRIGATION SHEETS I101 & I102 - IDENTIFY IN THE |
| | NARRATIVE THE SPECIFIC CHANGES THAT HAVE BEEN MADE TO |
| | THESE DRAWINGS.WPB AMEND. TO FBC SEC. 107.2.1.A |
| | REVISION APPLICATION SHOULD BE SUBMITTED UNDER THE |
| | IRRIGATION PERMIT. |
| | 3) SHT. A101C - SHOW THE LENGTH AND WIDTH DIMENSIONS OF |
| | TOILET ROOM #168. SHOW THE WIDTH OF THE LAVATORY |
| | COUNTERTOP, AND SHOW THE REQUIRED CLEAR FLOOR SPACE FOR |
| | THE WATER CLOSET AND THE LAVATORY AND THE DIMENSIONS OF |
| | EACH CLEAR FLOOR SPACE.COMPLY WITH 2010 |
| | FBC-ACCESSIBILITY SECS. 604.3.1, 606.2. |
| | 4) SHT.A103A - SHOW THE LENGTH AND WIDTH DIMENSIONS OF |
| | TOILET ROOM #838. SHOW THE WIDTH OF THE LAVATORY |
| | COUNTERTOP, AND SHOW THE REQUIRED CLEAR FLOOR SPACE FOR |
| | THE WATER CLOSET AND THE LAVATORY AND THE DIMENSIONS OF |
| | EACH CLEAR FLOOR SPACE.COMPLY WITH 2010 |
| | FBC-ACCESSIBILITY SECS. 604.3.1, 606.2. |
| | 5) SHT.A104A - SHOW THE WIDTH OF THE LAVATORY |
| | COUNTERTOP IN TOILET ROOM #938.. |
| | 6) SHT.A401A - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. |
| | 7) SHT. A401B - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. |
| | 8)SHT. A401B - ADA BATH - SHOW THE REQUIRED 60 INCHES |
| | WIDE BY 56 INCHES DEEP CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET PER THE FBC- ACCESSIBILITY SEC.233.3,809.4, |
| | 604.3. |
| | 9) SHT. A401C - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. |
| | 10) SHT. A402 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. . |
| | 11) SHT. A403 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. |
| | 12) SHT. A404 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. |
| | 13) SHT. A405 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. |
| | 14) SHT. A406 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. |
| | 15) SHT. A407 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. |
| | 16) SHT. A408 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. |
| | 17) SHT. A410 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. |
| | 18) SHT. A412 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | IN THE BATHROOMS SHALL BE CENTERED ON THE FIXTURE PER |
| | THE FAIR HOUSING ACT ACCESSIBILITY GUIDELINES REQ. #7 |
| | (2) AND FIGURE FHAG- 7 (C). CLEARLY SHOW THIS ON THE |
| | PLAN. |
| | 19) SHT. P101C - BREAKROOM #167 - THE CONDENSATE WASTE |
| | CANNOT DISCHARGE TO THE HAND SINK/SANITARY SYSTEM PER |
| | CITY OF WPB CODE OF ORDINANCES CHAPT. 90, SEC. 90-126 |
| | (B) (5). |
| | 20) SHT. P502 - THE DRAWING SHOWS THE DELETION OF TWO |
| | RECIRCULATING PUMPS FOR THE HOT WATER RECIRCULATION |
| | SYSTEM AND THE BOOSTER PUMP BEING USED TO SERVE THE |
| | RECIRCULATION SYSTEM. THE WATER HEATER/STORAGE TANK |
| | DETAIL STILL SHOWS A RECIRCULATION PUMP NEAR THE |
| | AQUASTAT. SHOULD THIS BE IDENTIFIED AS THE BOOSTER |
| | PUMP? CLARIFY. |
| | 21) PLEASE CLARIFY WITH A NARRATIVE AS TO HOW THE |
| | INSTALLATION OF A BOOSTER PUMP THAT WILL OPERTE WHEN |
| | THE PRESURE FALLS BELOW 100 PSI WILL MEET THE INTENT OF |
| | COMPLYING WITH 2010 FBC-PLUMBING SEC.607.2 FOR |
| | MAINTAINING THE TEMPERATURE IN ACCORDANCE WITH THE 2010 |
| | FBC-ENERGY CODE SEC. 504. THE PREVIOUS RECIRCULATING |
| | PUMPS WERE WIRED TO AN AQUASTAT WHEREAS THE BOOSTER |
| | PUMP APPEARS TO BE WIRED TO PRESSURE SENSORS. I AM |
| | CONFUSED. PLEASE CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |