| Plan Review Notes For Permit 17100879 |
| Permit Number |
17100879 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-24 10:14:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE 2010 | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. SHEET A401B, DETAILS 1B, 9, THE BATHROOM ENTRY DOOR | | | WAS REMOVED; HOW DOES ONE ENTER THE ROOM? FBC 107. | | | | | | 2. A403, THE ELEVATION DETAIL AND FLOOR PLAN (DETAIL 1) | | | APPEAR TO CONFLICT. WHEN SCALED, 8" IS SHOWN FROM | | | TOILET TO COUNTER, 21" SHOWN IN DETAIL 11. | | | | | | 3. CIVIL,LANDSCAPE, AND IRRIGATION SHEETS WERE | | | SUBMITTED. PLEASE COORDINATE WITH ENGINEERING, ZONING, | | | AND PLUMBING. IT APPEARS THAT THESE SHEETS SHOULD BE | | | SUBMITTED AS REVISIONS TO THE PERMITS ASSOCIATED WITH | | | THE WORK, FBC 107. | | | | | | |
|