| Notes |
| Date |
Text |
| 2017-12-27 14:17:48 | 1) SHT. P2 - THE GREASE TRAP DETAIL NOTES A 100 GPM | | | UNIT BUT THE PLANS SHOW A 50/75 GPM UNIT. CLARIFY. | | | 2) AN AIR ADMITTANCE VALVE (AAV) CAN BE USED ON A | | | GREASE INTERCEPTOR AS LONG AS THEY ARE NOT SUBJECT TO | | | POSITIVE PRESSURE PER THE MANUFACTURER (STUDOR) OF THE | | | AAV. CONFIRMATION OF THIS WILL NEED TO BE PROVIDED FROM | | | SCHIER. | | | 3) SUBMIT TWO COPIES OF OF THE MANUFACTURER'S | | | INSTALLATION GUIDE FOR THIS UNIT. WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|