Plan Review Notes
Plan Review Notes For Permit 17100875
Permit Number 17100875
Review Stop P
Sequence Number 2
Notes
Date Text
2017-12-27 14:17:481) SHT. P2 - THE GREASE TRAP DETAIL NOTES A 100 GPM
 UNIT BUT THE PLANS SHOW A 50/75 GPM UNIT. CLARIFY.
 2) AN AIR ADMITTANCE VALVE (AAV) CAN BE USED ON A
 GREASE INTERCEPTOR AS LONG AS THEY ARE NOT SUBJECT TO
 POSITIVE PRESSURE PER THE MANUFACTURER (STUDOR) OF THE
 AAV. CONFIRMATION OF THIS WILL NEED TO BE PROVIDED FROM
 SCHIER.
 3) SUBMIT TWO COPIES OF OF THE MANUFACTURER'S
 INSTALLATION GUIDE FOR THIS UNIT. WPB AMEND. TO FBC
 SEC. 107.2.1.
  