| Date |
Text |
| 2017-11-03 12:15:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO DO A |
| | COMPREHENSIVE REVIEW OF THE PROPOSES. |
| | |
| | IF THE WORK IS LIMITED TO TRANFET SWITCHES AND REMOTE |
| | PANELS, DETAILS AND SPECIFICS SHALL BE PROVIDED TO |
| | THOSE PIECES OF EQUIPMENT. DETAILS WITHIN THE ROOM/ |
| | WALL/ AREA OR SPACE SHALL BE PROVIDED. |
| | |
| | 2) IS THIS PROJECT A NEW INSTALLED GENERATOR OR |
| | MODIFICATIONS TO AN EXISTING ONE? |
| | |
| | PLEASE PROVIDE INFORMATION |
| | |
| | |
| | 3) THERE IS A CONCRETE SLAB SHEET INDICATED. IS THIS |
| | SLAB FOR A NEW GENERATOR INSTALL OR REPLACEMENT FOR AN |
| | EXISITNG ONE? |
| | |
| | PLEASE PROVIDE INFORMATION |
| | |
| | |
| | 4) THERE IS NO LOCATION INDICATED WHERE THE WORK WILL |
| | BE DONE ON ANY PLAN SHEET. |
| | |
| | PROVIDE THE LOCATION OR AREA OF WORK. |
| | |
| | |
| | |
| | 5) THERE ARE NO EQUIPMENT SPECIFICATIONS SHEETS. |
| | |
| | PROVIDE SPEC SHEETS |
| | |
| | |
| | |
| | 6) WILL THIS GENERATOR BE SUPPLYING ANY LIFE SAFETY |
| | EQUIPMENT? IF SO, ALL INSTALLATIONS SHALL COMPLY WITH |
| | NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER |
| | SYSTEMS, 2010 EDITION.AND SHALL BE INSPECTED AND TESTED |
| | PER THE CODE. |
| | |
| | PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. |
| | |
| | |
| | |
| | 7) ALL ELECTRICAL INSTALLTIONS SHALL COMPLY WITH NFPA |
| | 70?, NATIONAL ELECTRICAL CODE?, 2011 EDITION. |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |