| Plan Review Notes For Permit 17100865 |
| Permit Number |
17100865 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-07 13:13:38 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | NOTE: SUBMISSIONS FOR THIS PERMIT ARE SEPARATE FROM | | | OTHER PERMITS THAT MAY OR MAY NOT BE OPEN ON THIS JOB | | | AND REQUIRE THE FOLLOWING: | | | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | | SEALED BY THE LICENSED DESIGN PROFESSIONAL OF RECORD | | | FOR GENERATOR INSTALLATION. FS 471.003(2)(H); 471.025; | | | FBC 107.2.1, 107.3.5 | | | 2. PROVIDE SPEC SHEET AND INSTALLATION MANUAL FOR | | | GENERATOR AND TRANSFER SWITCH. | | | 3. PROVIDE LOAD CALCULATION FOR LOADS SUPPLIED BY | | | GENERATOR TO VERIFY CAPACITY OF THE GENERATOR IS | | | SUFFICIENT. NEC 220, NEC 700.4 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|