Plan Review Notes
Plan Review Notes For Permit 17100865
Permit Number 17100865
Review Stop E
Sequence Number 1
Notes
Date Text
2017-11-07 13:13:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 NOTE: SUBMISSIONS FOR THIS PERMIT ARE SEPARATE FROM
 OTHER PERMITS THAT MAY OR MAY NOT BE OPEN ON THIS JOB
 AND REQUIRE THE FOLLOWING:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE LICENSED DESIGN PROFESSIONAL OF RECORD
 FOR GENERATOR INSTALLATION. FS 471.003(2)(H); 471.025;
 FBC 107.2.1, 107.3.5
 2. PROVIDE SPEC SHEET AND INSTALLATION MANUAL FOR
 GENERATOR AND TRANSFER SWITCH.
 3. PROVIDE LOAD CALCULATION FOR LOADS SUPPLIED BY
 GENERATOR TO VERIFY CAPACITY OF THE GENERATOR IS
 SUFFICIENT. NEC 220, NEC 700.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  