Plan Review Notes
Plan Review Notes For Permit 17100865
Permit Number 17100865
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-05 13:39:462014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100865
 ADD: 1101 54TH ST.
 CONT: TRITON ELECTRIC CO.
 TEL: 321-246-8262
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 05/2018
 ACTION: DENIED
  
 1) PLEASE NOTE THE SHEET GS-1.0 PROVIDES THE DETAILS
 FOR THE GENERATOR SLAB BUT THERE IS NO INFORMATION ON
 THE ANCHORING THE GENERATOR AND DAY TANK TO THE SLAB.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 2) IN THE GENERAC PACKAGE IT APPEARS THE STANDARD
 ENCLOSURE FOR A 350 KW BUT THE PACKAGE DOES NOT PROVIDE
 THE ANCHORAGE OF THE DAY TANK TO THE SLAB NOR IS THERE
 DETAILS OF HOW THE DAY TANK AND GENERATOR ARE TO BE
 ANCHORED/ JOINED TOGETHER. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
2017-12-27 17:14:32SENT TO JW'S DESK. CT


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved