| Plan Review Notes For Permit 17100863 |
| Permit Number |
17100863 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-31 15:38:49 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | PERMIT #17100863 | | | 10/31/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED AC DUCT LAYOUT PLAN IS NOT SUITABLE | | | FOR REVIEW. ALL PLANS SHALL BE DRAWN NEATLY AT A | | | MINIMUM 1/8" SCALE, AND SHALL BE OF SUFFICIENT CLARIFY | | | TO INDICATE THE EXTENT OF THE WORK PROPOSED AND SHOW IN | | | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THE | | | CODE- PLEASE REVIEW SECTIONS 107.2.1 AND 107.2.1.4 WPB | | | AMENDMENTS TO THE FBC. PLEASE MAKE THE FOLLOWING | | | CORRECTIONS. | | | | | | A) PROVIDE TWO SEPARATE FLOOR PLAN DRAWINGS- FIRST | | | FLOOR AND SECOND FLOOR. | | | B) SHOW THE ROOMS ON EACH FLOOR AND IDENTIFY THEM. | | | C) SHOW THE ACTUAL LOCATION OF THE EXISTING AIR | | | HANDLER- THE SUBMITTED DRAWING DOES NOT SHOW IT IN THE | | | HOUSE. | | | D) SHOW THE DIMENSIONS OF THE DIFFUSERS AND RETURN | | | GRILLS. | | | E) SHOW THE SUPPLY CFMS AT EACH DIFFUSER. | | | F) SHOW HOW AIR IS BEING RETURNED FROM THE BEDROOMS- | | | TRANSFER GRILLS, TRANSFER DUCTS? | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|