2017-10-31 15:38:491ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17100863
 10/31/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED AC DUCT LAYOUT PLAN IS NOT SUITABLE
 FOR REVIEW. ALL PLANS SHALL BE DRAWN NEATLY AT A
 MINIMUM 1/8" SCALE, AND SHALL BE OF SUFFICIENT CLARIFY
 TO INDICATE THE EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THE
 CODE- PLEASE REVIEW SECTIONS 107.2.1 AND 107.2.1.4 WPB
 AMENDMENTS TO THE FBC. PLEASE MAKE THE FOLLOWING
 CORRECTIONS.
  
 A) PROVIDE TWO SEPARATE FLOOR PLAN DRAWINGS- FIRST
 FLOOR AND SECOND FLOOR.
 B) SHOW THE ROOMS ON EACH FLOOR AND IDENTIFY THEM.
 C) SHOW THE ACTUAL LOCATION OF THE EXISTING AIR
 HANDLER- THE SUBMITTED DRAWING DOES NOT SHOW IT IN THE
 HOUSE.
 D) SHOW THE DIMENSIONS OF THE DIFFUSERS AND RETURN
 GRILLS.
 E) SHOW THE SUPPLY CFMS AT EACH DIFFUSER.
 F) SHOW HOW AIR IS BEING RETURNED FROM THE BEDROOMS-
 TRANSFER GRILLS, TRANSFER DUCTS?
  