Plan Review Notes
Plan Review Notes For Permit 17100851
Permit Number 17100851
Review Stop B
Sequence Number 2
Notes
Date Text
2018-03-09 15:42:35RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 NEW COMMENT:
 A) FORM R405-2017 SUBMITTED NOW IS INCORRECT. THIS FORM
 IS FOR THE 2017 CODE. THIS BUILDING IS BEING REVIEWED
 UNDER THE 2014 CODE. PROVIDE CORRECT FORM. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) ENERGY CALCULATIONS CALL FOR ELECTRIC WATER HEATER
 ON ITEM #14. PLANS CALL FOR GAS WATER HEATER. REVISE TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) WINDOW INFORMATION SHOWN ON PAGE 3 OF 4 OF FORM
 SUBMITTED; CLARIFY WHAT KIND OF FRAME IS "TIM". SEC.
 107.2.1 CITY AMENDMENTS. SEE PRODUCT APPROVALS
 SUBMITTED.
  
 D) THE NAME OF THE "BLOCKS" INFORMATION ON PAGE 2 OF 4
 SPECIFIES "ENTIRE HOUSE". ACCORDING TO AREA SHOWN ON
 PAGE ONE (414 S.F.) THIS BLOCK IS FOR THE ADDITION NOT
 FOR ENTIRE HOUSE. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) CLARIFY WHY THERE ARE NO OCCUPANTS ON THE MASTER
 BEDROOM. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 2- HURRICANE FABRIC NOA 15-0316.09 SUBMITTED: PROVIDE
 FLOOR PLAN SKETCH AND COMPLETE INSTALLATION SCHEDULE.
 SEE CITY SAMPLE FOR REQUIRED INFORMATION. INSTALLATION
 SCHEDULE SUBMITTED IS INCOMPLETE. NEED TO SPECIFY
 OPENING SIZES, LOCATION, ALL MOUNTING CONDITIONS,
 ANCHORS, SPACING, ETC. TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
  
 3- TRUSS PACKAGE SUBMITTED;
 A) ALL TRUSS DRAWINGS NEED THE TRUSS ENGINEER SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 F.S.
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  