| 2018-03-09 15:42:35 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED: |
| | NEW COMMENT: |
| | A) FORM R405-2017 SUBMITTED NOW IS INCORRECT. THIS FORM |
| | IS FOR THE 2017 CODE. THIS BUILDING IS BEING REVIEWED |
| | UNDER THE 2014 CODE. PROVIDE CORRECT FORM. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | B) ENERGY CALCULATIONS CALL FOR ELECTRIC WATER HEATER |
| | ON ITEM #14. PLANS CALL FOR GAS WATER HEATER. REVISE TO |
| | MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | C) WINDOW INFORMATION SHOWN ON PAGE 3 OF 4 OF FORM |
| | SUBMITTED; CLARIFY WHAT KIND OF FRAME IS "TIM". SEC. |
| | 107.2.1 CITY AMENDMENTS. SEE PRODUCT APPROVALS |
| | SUBMITTED. |
| | |
| | D) THE NAME OF THE "BLOCKS" INFORMATION ON PAGE 2 OF 4 |
| | SPECIFIES "ENTIRE HOUSE". ACCORDING TO AREA SHOWN ON |
| | PAGE ONE (414 S.F.) THIS BLOCK IS FOR THE ADDITION NOT |
| | FOR ENTIRE HOUSE. REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | E) CLARIFY WHY THERE ARE NO OCCUPANTS ON THE MASTER |
| | BEDROOM. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | 2- HURRICANE FABRIC NOA 15-0316.09 SUBMITTED: PROVIDE |
| | FLOOR PLAN SKETCH AND COMPLETE INSTALLATION SCHEDULE. |
| | SEE CITY SAMPLE FOR REQUIRED INFORMATION. INSTALLATION |
| | SCHEDULE SUBMITTED IS INCOMPLETE. NEED TO SPECIFY |
| | OPENING SIZES, LOCATION, ALL MOUNTING CONDITIONS, |
| | ANCHORS, SPACING, ETC. TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 3- TRUSS PACKAGE SUBMITTED; |
| | A) ALL TRUSS DRAWINGS NEED THE TRUSS ENGINEER SEAL AND |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| | EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD |
| | DRAWINGS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |