2017-11-15 16:46:591ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE ENERGY CALCULATIONS SHOW A ELECTRIC TANKLESS
 WATER HEATER THE PLANS SHOW IT ON THE EXTERIOR OF
 BUILDING, NORMALLY ELECTRIC TANKLESS HEATERS ON NOT
 DESIGNED FOR EXTERIOR INSTALLATIONS THE ELECTRIC PANEL
 SHOWS 30 AMP BREAKERS FOR THE WATER HEATER MOST
 TANKLESS ARE 40 AMP AND ABOVE PLEASE PROVIDE
 MANUFACTURE SPECIFICATIONS TO CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 2. SHOW LOCATION OF EXISTING WATER HEATER. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  