2017-11-22 14:32:45RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- RETURN AIR TRANSFER DUCT SIZE SPECIFIED FOR THE
 MASTER BEDROOM DOESN'T COMPLY WITH SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014). NEED AT LEAST 15"
 DIAMETER TRANSFER DUCT. REVISE A/C PLAN AS REQUIRED.
 NOTE: DUCT SIZE IS BASED ON ALL THE SUPPLY AIR TO THE
 MASTER BEDROOM, INCLUDING BATHROOM AND CLOSETS.
  
 2- IT LOOKS LIKE THE SAME PERSON DOING THE ENERGY
 CALCULATIONS IS DOING THE EQUIPMENT SIZING
 CALCULATIONS. ENERGY CALCULATIONS NEED TO BE REVISED.
 SEE BUILDING REVIEW COMMENTS. REVISE THE EQUIPMENT
 SIZING CALCULATIONS BASED ON THE REVISED ENERGY
 CALCULATIONS. SEC. R403.6 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 3- A/C PLAN TO LIST THE EQUIPMENT LISTED IN THE
 EQUIPMENT SIZING CALCULATIONS. SEC. R403.6 FBC-ENERGY
 CONSERVATION AND SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  