| 2017-11-22 14:32:45 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- RETURN AIR TRANSFER DUCT SIZE SPECIFIED FOR THE |
| | MASTER BEDROOM DOESN'T COMPLY WITH SEC. M1602.4 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). NEED AT LEAST 15" |
| | DIAMETER TRANSFER DUCT. REVISE A/C PLAN AS REQUIRED. |
| | NOTE: DUCT SIZE IS BASED ON ALL THE SUPPLY AIR TO THE |
| | MASTER BEDROOM, INCLUDING BATHROOM AND CLOSETS. |
| | |
| | 2- IT LOOKS LIKE THE SAME PERSON DOING THE ENERGY |
| | CALCULATIONS IS DOING THE EQUIPMENT SIZING |
| | CALCULATIONS. ENERGY CALCULATIONS NEED TO BE REVISED. |
| | SEE BUILDING REVIEW COMMENTS. REVISE THE EQUIPMENT |
| | SIZING CALCULATIONS BASED ON THE REVISED ENERGY |
| | CALCULATIONS. SEC. R403.6 FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | |
| | 3- A/C PLAN TO LIST THE EQUIPMENT LISTED IN THE |
| | EQUIPMENT SIZING CALCULATIONS. SEC. R403.6 FBC-ENERGY |
| | CONSERVATION AND SEC. 107.3.5.3(10) CITY AMENDMENTS. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| | EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD |
| | DRAWINGS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |