Plan Review Notes
Plan Review Notes For Permit 17100851
Permit Number 17100851
Review Stop B
Sequence Number 1
Notes
Date Text
2017-11-15 18:29:12RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS CAN BE DONE LATER AFTER THE PLANS ARE
 APPROVED AND STAMPED BY OUR OFFICE.
  
 2- AREA CALCULATIONS SHOWN ON SHEET C.1 DON'T MATCH
 AREA CALCULATIONS SHOWN ON SHEET 1.1 AND SHEET 2.1.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- WINDOW ON BEDROOM #1 WAS BLOCKED TO ALLOW FOR THE
 MASTER BEDROOM ADDITION. SPECIFY TYPE AND SIZE OF
 WINDOW TO BE BLOCKED AND TYPE AND SIZE OF REMAINING
 WINDOW TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS. SEC. 704 FBC-EXISTING BUILDING, 5TH
 EDITION (2014).
  
 4- TYPE OF FOOTING F-2 SHOWN ON FOUNDATION PLAN ON
 SHEET 2.1 DOESN'T MATCH FOOTING SHOWN ON TYPICAL WALL
 SECTION ON SHEET 5.1. VERIFY TYPE OF FOOTING AND SIZE
 TO MATCH. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH ITEM #8(A) BELOW.
  
 5- IT IT'S NOT CLEAR HOW MANY RISERS ARE REQUIRED BY
 THE NEW EXTERIOR DOOR AT THE NEW MASTER BATHROOM AREA.
 FLOOR PLAN ON SHEET 2.1 SHOWS 2 RISERS, WHILE NORTH
 ELEVATION ON SHEET 4.1 SHOWS 3 RISERS. REVISE AS
 REQUIRED TO MATCH. ALSO, LANDING AT THE NEW EXTERIOR
 DOOR MAY BE REQUIRED. SEE SEC. R311.3.2 FBC-RESIDENTIAL
 AND REVISE AS REQUIRED.
  
 6- REVISE THE ALTERATION LEVEL SPECIFIED ON THE PROJECT
 DATA ON SHEET 2.1. ACCORDING TO SEC. 505 FBC-EXISTING
 BUILDING, 5TH EDITION (2014) AND SCOPE OF WORK SHOWN ON
 PLANS THIS IS ALTERATION LEVEL 3 NOT ALTERATION LEVEL
 2. REVISE AS REQUIRED.
  
 7- REVISE THE CORNER DISTANCE "A" SPECIFIED ON THE
 COMPONENT AND CLADDING PRESSURE ZONES TABLE ON SHEET
 4.1. ACCORDING TO FOOTNOTE OF FIGURE R301.2(7)
 FBC-RESIDENTIAL, THE LETTER "A" IS 4 FEET IN ALL CASES
 NOT 3 FEET. REVISE AS REQUIRED.
  
 8- SOIL TEST REPORT SUBMITTED:
 A) ARCHITECT OF RECORD TO REVIEW CONCLUSIONS ON THE
 SOIL TEST REPORT AND REVISE FOOTING DESIGN ACCORDINGLY
 OR ACKNOWLEDGE IN WRITING THAT DESIGNED FOOTINGS ARE
 ADEQUATE DESPITE THE SOIL TEST REPORT CONCLUSIONS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 B) PROVIDE 2 COPIES. ONLY ONE COPY WAS SUBMITTED. SEC.
 107.1 CITY AMENDMENTS.
  
 9- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AND
 DATE THE BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER, BUILDER, PERMIT OFFICE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) REVISE WINDOW FRAME MATERIAL SPECIFIED ON PAGE 4 OF
 5. WINDOWS AND DOORS PRODUCT APPROVALS SUBMITTED ARE
 FOR ALUMINUM WINDOWS AND DOORS NOT VINYL. REVISE AS
 REQUIRED. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 D) REVISE THE WINDOWS OVERHANG SEPARATION ON PAGE 4 OF
 5 TO MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 NOTE: LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE DEFAULT FACTOR FOR GLAZING.
  
 10- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 WINDOWS AND DOORS SHOWING COMPLIANCE WITH THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 SUBMITTED. SEC. R405.4.3 FBC-ENERGY CONSERVATION.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A) SINGLE HUNG WINDOWS. NEED TO PROVIDE 2 COPIES. ONLY
 ONE COPY OF NOA 15-0512.10 WAS SUBMITTED. ALSO,
 DRAWINGS SUBMITTED ARE TOO SMALL. PLEASE PROVIDE COPY
 OF DRAWINGS THAT ARE PRINTED IN THE LANDSCAPE FORMAT.
 THIS WAY DRAWINGS ARE MORE LEGIBLE.
  
 B) FIXED WINDOWS. NEED TO PROVIDE 2 COPIES. ONLY ONE
 COPY OF NOA 15-0413.03 WAS SUBMITTED. ALSO, DRAWINGS
 SUBMITTED ARE TOO SMALL. PLEASE PROVIDE COPY OF
 DRAWINGS THAT ARE PRINTED IN THE LANDSCAPE FORMAT. THIS
 WAY DRAWINGS ARE MORE LEGIBLE.
  
 C) ALUMINUM OUTSWING GLAZED DOOR. NEED TO PROVIDE 2
 COPIES. ONLY ONE COPY OF NOA 14-1015.04 WAS SUBMITTED.
 ALSO, DRAWINGS SUBMITTED ARE TOO SMALL. PLEASE PROVIDE
 COPY OF DRAWINGS THAT ARE PRINTED IN THE LANDSCAPE
 FORMAT. THIS WAY DRAWINGS ARE MORE LEGIBLE.
  
 D) OVERHEAD GARAGE DOOR. NEED TO PROVIDE 2 COPIES. ONLY
 ONE COPY OF NOA 16-0330.02 WAS SUBMITTED. ALSO,
 DRAWINGS SUBMITTED ARE TOO SMALL. PLEASE PROVIDE COPY
 OF DRAWINGS THAT ARE PRINTED IN THE LANDSCAPE FORMAT.
 THIS WAY DRAWINGS ARE MORE LEGIBLE.
  
 E) HURRICANE FABRIC. NEED TO PROVIDE 2 COPIES. ONLY ONE
 COPY OF NOA 15-0316.09 WAS SUBMITTED.
 NOTE: NEED TO PROVIDE COMPLETE INSTALLATION SCHEDULE
 FOR THE INSTALLATION OF THE HURRICANE FABRIC. SEE CITY
 SAMPLE OF INSTALLATION SCHEDULE.
  
 F) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 12- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]