| Plan Review Notes For Permit 17100808 |
| Permit Number |
17100808 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-27 15:14:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE NO DIMENSIONS INDICATED OF THE WIDTH OF | | | THE DRIVE LANESOF THE SOUTH GATE. FIRE DEPARTMENT | | | VEHICLES SHALL HAVE UNRESTRICTED ACCESS WIDTH OF A | | | MINIMUM 12'. | | | | | | PLEASE PROVIDE THE DIMENSION TO THE EDGE OF THE BOLLARD | | | FROM BOTH CURBS. | | | | | | | | | | | | 2) THERE IS NO INDICATIONS OF HOW THE FIRE DEPARTMENT | | | WILL GAIN ACCESS THROUGH THESE GATES; 24 HOUR EMERGENCY | | | ACCESS IS REQUIRED. A KNOX KEY SWITCH IS REQUIRED FOR | | | ACCESS. | | | | | | PLEASE PROVIDE DETAILS ON HOW THE FD WILL GAIN ACCESS | | | THRU THESE GATES AND/ OR PROVIDE A KNOX KEY SWITCH AT | | | EACH LOCATION. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|