2017-10-25 13:03:58FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER DIAGRAM IS ONCOMPLETE PAGE E101
  
 PLAN SHOWS 5 PANELS SCHEDULES BUT ONLY 4 PANELS SHOWN
 ON DRAWINGS.
  
 PLANS SHOWS GENERATOR, WHICH IS NOT SHOWN ON RISER
 DIAGRAM. SEPARATE PERMIT REQUIRED
  
 RISER SHOWS 2 CONDUITS FROM METER TO MAIN BUT NO WIRE
 SIZES, SAME FROM MAIN TO GUTTER.
  
 FAULT CURRENT IS SHOWN AT 22,000 HOW WAS THIS
 CALCULATED.
  
 PLAN SHOWS SEVERAL OUTLETS THAT ARE OUT SIDE AND NOT
 GFCI PROTECTED
  