| Plan Review Notes For Permit 17100796 |
| Permit Number |
17100796 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-25 13:03:58 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | RISER DIAGRAM IS ONCOMPLETE PAGE E101 | | | | | | PLAN SHOWS 5 PANELS SCHEDULES BUT ONLY 4 PANELS SHOWN | | | ON DRAWINGS. | | | | | | PLANS SHOWS GENERATOR, WHICH IS NOT SHOWN ON RISER | | | DIAGRAM. SEPARATE PERMIT REQUIRED | | | | | | RISER SHOWS 2 CONDUITS FROM METER TO MAIN BUT NO WIRE | | | SIZES, SAME FROM MAIN TO GUTTER. | | | | | | FAULT CURRENT IS SHOWN AT 22,000 HOW WAS THIS | | | CALCULATED. | | | | | | PLAN SHOWS SEVERAL OUTLETS THAT ARE OUT SIDE AND NOT | | | GFCI PROTECTED | | | |
|