| 2017-11-14 15:00:48 | 11/14/2017 GAS 2ND REVIEW**DENIED** COMMENTS #2 AND #3 |
| | HAVE NOT BEEN ADDRESSED |
| | |
| | |
| | 1) YOU MUST INCLUDE EXISTING BTU LOADS ON THE SYSTEM |
| | AND INCLUDE THEM ON THE ISOMETRIC DRAWNING. THE PLANS |
| | INDICATE AN EXISTING GAS METER. THE BTU LOAD OF THE |
| | EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU |
| | LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS |
| | PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST |
| | BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A |
| | GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF |
| | EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE |
| | PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION.. FGC SECS. 401.4, 401.8, 402.1, 402.2, |
| | 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2, |
| | G2413.3. |
| | |
| | 2) YOU MUST INCLUDE ALL SIZING TABLES (2 COPIES) FOR |
| | EACH PIPING MATERIAL BEING USED OR EXISTING. YOU HAVE |
| | ONLY PROVIDED THE SIZING TABLE FOR P.E PIPING. SUBMIT |
| | TWO COPIES OF THE APPLICABLE SIZING TABLES USED TO SIZE |
| | THE GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS |
| | SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR |
| | OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS |
| | SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4, |
| | 401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) |
| | OR 2014 FBC-RES. SEC. G2412.4, G2412.8, G2413.1, |
| | G2413.2, & G2413.3 |
| | |