| 2017-11-01 06:31:04 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF SIGNED, SEALED AND DATED | | | GENERATOR PAD AND ANCHORING DETAILS FOR EXPOSURE | | | CATEGORY C AND A 170 MPH VULT WIND SPEED. THE DOCUMENTS | | | ARE REQUIRED TO HAVE THE ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE | | | NOT ACCEPTABLE. FAC 61G15 - 23.002 | | | | | | 2) THE ENGINEER THAT IS ON THE SLAB ANCHORING PLANS, | | | RONALD H. WILSON P.E. LICENSE NO. 9710, HAS HAD HIS FL | | | ENGINEERING LICENSE REVOKED SINCE 2/28/2017. SUBMIT | | | PLANS FROM A CURRENTLY LICENSED FL ENGINEER. FS 471 | | | |
|