| Plan Review Notes For Permit 17100784 |
| Permit Number |
17100784 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-25 09:47:45 | 1) SHT. PP130C AND SHT.PP501 - SHOW THE PIPE SIZES FOR | | | ALL THE ADDED PIPING/DRAINS. | | | 2) SHT. PP160A - IF THESE DECK DRAINS ARE OPEN TO THE | | | ATMOSPHERE WHERE THEY WILL BE DRAINING RAINWATER, | | | SUPPLY THE THE SQUARE FOOT AREA BEING DRAINED BY EACH | | | DECK DRAIN. THE EXISTING SYSTEM SHALL BE CHECKED TO | | | ENSURE THAT IT IS ADEQUATELY SIZED TO HANDLE THE ADDDED | | | AREA. BEING DRAINED IN ACCORDANCE WITH FBC-PLUMBING | | | TABLE 1106.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|