| 2017-11-03 11:54:24 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A001 UNDER SCOPE OF WORK IT LISTS UNITS 105-110 |
| | THE PLAN AND PERMIT APP SHOWS UNIT 115 PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. THE KITCHEN SINK SHALL COMPLY WITH FBC ACC 606 SHT. |
| | A-801 DETAIL #2 SHOWS 36" TO TOP OF COUNTER THAT DOES |
| | NOT COMPLY PLEASE CLARIFY. |
| | |
| | 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 |
| | DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| | DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS |
| | DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW. |
| | |
| | 4. WALLS AROUND THE JANITORS SINK SHALL COMPLY WITH FBC |
| | 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF |
| | A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 5. THE KITCHEN SINK SHALL BE SUPPLIED WITH HOT WATER |
| | MIN 110DEG. THE LAVATORY REQUIRES TEMPERED WATER UNDER |
| | 110DEG. THE KITCHEN SHALL NOT BE SUPPLIED THROUGH THE |
| | WATER TEMPERATURE LIMITING DEVICE USED FOR TEMPERED |
| | WATER. PER FBC PL 607.1 AND 416.5 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |