| 2018-04-16 16:49:29 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN |
| | NOTED AS CORRECTED. ITEMS REMAINING HAVE NOT BEEN |
| | ADDRESSED OR NEED FURTHER CORRECTION. SEE ADDITIONAL |
| | COMMENTS IN PARENTHESES. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2, |
| | 405.2.2.2 (NOT PROVIDED)(NOT PROVIDED ON 5TH |
| | REVIEW)(STILL NOT PROVIDED ON 6TH REVIEW)(7TH REVIEW - |
| | SOME OCCUPANCY SENSORS WERE ADDED, BUT NOT ALL LIGHTS |
| | SHOW THE AUTOMATIC CONTROL REQUIRED PER CODE.) |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION |
| | PROVIDED SHOWS DEMAND FACTORS THAT ARE NOT PERMITTED |
| | PER CODE. PROVIDE ACCURATE LOAD CALCULATION.)(LOAD |
| | CALCULATION STILL NOT PER CODE ON 5TH REVIEW.)(STILL |
| | NOT CORRECT ON 6TH REVIEW. THE WATER HEATER LOAD CAN |
| | NOT BE CALCULATED AT 50%. WHEN CALCULATED AT 100%, THE |
| | EXISTING SERVICE IS TOO SMALL. PROVIDE CORRECTION.)(7TH |
| | REVIEW - LOAD CALCULATION STILL NOT CORRECT. A FEEDER |
| | MUST BE SIZED TO HANDLE 125% OF THE CONTINUOUS LOAD |
| | PLUS 100% OF THE NON-CONTINUOUS LOAD. YOU HAVE NOT |
| | CORRECTLY ADDED ALL CONTINUOUS LOADS. PANEL B IS SHOWN |
| | WITH A LOAD THAT EXCEEDS THE FEEDER SIZE AND OCP SIZE. |
| | MAIN SERVICE LOAD MAY ALSO EXCEED THE FEEDER SIZE AND |
| | OCP WHEN COMPLETED CORRECTLY. WHEN LOAD CALCULATION IS |
| | ACCURATE, THIS WILL BE USED TO SIZE FEEDERS AND OCP FOR |
| | PANELS.) |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. FEE ADDED. |
| | 10. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |