| 2018-01-26 08:50:39 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17100775 |
| | ADD: 525 25TH ST. |
| | CONT: TOU INC. |
| | TEL: 561-255-1417 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: FRI. JAN. 26/2018 |
| | ACTION: DENIED |
| | |
| | HOLD ON PERMIT!!!!! STILL NEED OWNERS SIGNATURE ON THE |
| | PERMIT APPLICATION!!!! |
| | |
| | 1-3) COMPLIED. |
| | |
| | 4) PROVISO: SHEET AE-1.0 ALSO INDICATES A RECEPTIONIST/ |
| | CASHIER SERVICE COUNTER BUT THERE ARE NO DETAILS |
| | PROVIDING CODE COMPLIANCE FOR THE 2014 |
| | FBC-ACCESSIBILITY CODE SECTIONS: |
| | 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK |
| | WRITING SURFACES SHALL COMPLY WITH 902.3. |
| | 902.3 HEIGHT. |
| | THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM |
| | AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 5) 3RD REQUEST. THE SHEET AE 3.0 STILL DOES NOT SHOW |
| | COMPLIANCE WITH THE MECHANICAL CODE, I DISCUSSED THIS |
| | WITH THE MECHANICAL PLANS EXAMINER, DEPENDING ON THE |
| | NEXT GENERATION OF PLANS THIS COMMENT STILL STANDS. |
| | THERE MAY BE SOFFITS TO BE BUILT TO HIDE EXHAUST AIR |
| | DUCTWORK AND OR ROOF TOP PENETRATIONS. |
| | |
| | THE MANICURES AND PEDICURES HAVE TO CATCH THE FUMES AT |
| | THE SOURCE, PLEASE REVIEW THE MECHANICAL COMMENT # 4 |
| | WILL NEED TO COMPLY WITH 2014 FBC-M TABLE 403, |
| | FOOTNOTES B & H, DEPENDING WHERE YOU BRING IN THE |
| | MAKE-UP AIR AND EXHAUST AIR YOU WILL HAVE EITHER WALL |
| | OR ROOF PENETRATIONS FOR THE NEW INTAKE AND EXHAUST |
| | FANS. PLEASE NOTE THERE MAYBE ADDITIONAL COMMENTS ABOUT |
| | ROOF TOP CURBS, INTAKE AND EXHAUST FANS AND THE |
| | ANCHORING OF THESE UNITS TO THE CURRENT WIND LOADS |
| | BECAUSE OF CODE REQUIREMENTS UNDER THE MECHANICAL CODE. |
| | FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | |
| | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |