| Date |
Text |
| 2017-10-20 10:58:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET AE 1.0 & LS 1.0 - THERE IS ARE INDICATIONS |
| | THAT THIS IS A MERCANTILE OCCUPANCY WITH AND OCCUPANCY |
| | LOAD OF 30ST/PERSON OR 27 TOTAL OCCUPANTS. |
| | |
| | ACCORDING TO THE FFPC, NPFA 101, THIS IS A BUSINESS |
| | OCCUPANCY.WITH AN OCCUPANCY LOAD OF 100 SF/PERSON, OR |
| | 10. |
| | |
| | PER CHAPTER 3, DEFINITIONS - 3.3.188.3* BUSINESS |
| | OCCUPANCY. AN OCCUPANCY USED FOR THE TRANSACTION OF |
| | BUSINESS OTHER THAN MERCANTILE. |
| | |
| | FOR GUIDANCE PURPOSES, ACCORDING TO THE APPENDIX - |
| | |
| | A.3.3.188.3 BUSINESS OCCUPANCY. BUSINESS OCCUPANCIES |
| | INCLUDE THE FOLLOWING: |
| | (1) AIR TRAFFIC CONTROL TOWERS (ATCTS) |
| | (2) CITY HALLS |
| | (3) COLLEGE AND UNIVERSITY INSTRUCTIONAL BUILDINGS, |
| | CLASSROOMS |
| | UNDER 50 PERSONS, AND INSTRUCTIONAL LABORATORIES |
| | (4) COURTHOUSES |
| | (5) DENTISTS? OFFICES |
| | (6) DOCTORS? OFFICES |
| | (7) GENERAL OFFICES |
| | (8) OUTPATIENT CLINICS (AMBULATORY) |
| | (9) TOWN HALLS |
| | |
| | SERVICE FACILITIES COMMON TO CITY OFFICE BUILDINGS, |
| | SUCH AS NEWSSTANDS, LUNCH COUNTERS SERVING FEWER THAN |
| | 50 PERSONS, BARBER SHOPS, AND BEAUTY PARLORS ARE |
| | INCLUDED IN THE BUSINESS OCCUPANCY GROUP. |
| | |
| | A NAIL SALON, THIS OCCUPANCY, FALLS UNDER THIS |
| | OCCUPANCY DEFINITION. |
| | |
| | ACCORDING TO CHAPTER 7, MEANS OF EGRESS, |
| | |
| | 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY |
| | BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE |
| | NUMBER OF PERSONS DETERMINED BY DIVIDING THE FLOOR AREA |
| | ASSIGNED TO THAT USE BY THE OCCUPANT LOAD FACTOR FOR |
| | THAT USE AS SPECIFIED IN TABLE 7.3.1.2, FIGURE |
| | 7.3.1.2(A), AND FIGURE 7.3.1.2(B). WHERE BOTH GROSS AND |
| | NET AREA FIGURES ARE GIVEN FOR THE SAME OCCUPANCY, |
| | CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA |
| | FIGURE TO THE GROSS AREA OF THE PORTION OF THE BUILDING |
| | DEVOTED TO THE USE FOR WHICH THE GROSS AREA FIGURE IS |
| | SPECIFIED AND BY APPLYING THE NET AREA FIGURE TO THE |
| | NET AREA OF THE PORTION OF THE BUILDING DEVOTED TO THE |
| | USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED. |
| | |
| | TABLE 7.3.1.2 OCCUPANT LOAD FACTOR INDICATES AN |
| | OCCUPANCY LOAD FACTOR OF 100 SQ FT/PERSON. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDED DETAIL |
| | JUSTIFICATION. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |