| 2018-11-13 15:46:20 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. WHERE IS THIS PANEL FED FROM? PROVIDE RISER DIAGRAM, |
| | SHOWING ALL DETAILS OF SERVICE EQUIPMENT, UNDERGROUND |
| | OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE |
| | AND FEED TO SUB-PANEL. SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1, |
| | RE3609.3; FBC 107.2.1 (NOT PROVIDED) |
| | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 (NOT |
| | PROVIDED. THIS IS FOR THE MAIN SERVICE THAT THE |
| | SUB-PANEL IS FED FROM. LOAD IS BEING ADDED TO THIS AND |
| | REVIEWER NEEDS TO KNOW THE CURRENT SIZE AND TOTAL |
| | CALCULATED LOAD.) |
| | 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, |
| | 225.32 (NOT PROVIDED IN THE NOTES IT STATES THE 60 AMP |
| | PANEL IS TO REMAIN, IN THE PANEL SCHEDULE IT STATES |
| | THAT A NEW PANEL WILL BE INSTALLED. WHICH IS CORRECT? |
| | CORRECT DISCREPANCY AND PROVIDE MAIN BREAKER IN PANEL |
| | OR DISCONNECT AS PREVIOUSLY STATED.) |
| | 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| | CIRCUIT. NEC 250.32; FBC RE3607.3 (NOT PROVIDED.) |
| | 6. CORRECTED. |
| | 7. TOILET # 2 IS SHOWN ON A 15 AMP BREAKER. A MINIMUM |
| | 20 AMP CIRCUIT IS REQUIRED FOR BATHROOM GFCI RECEPTACLE |
| | OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC |
| | RE3703.4 (NOT CORRECTED.) |
| | 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC |
| | 110.3 (NOT PROVIDED.) |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15 |
| | AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC |
| | RE3902.12 (NOT PROVIDED.) |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |