| 2018-04-09 09:58:36 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT 17100735 | | | 4/9/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COMMENT #2 FROM THE PREVIOUS REVIEW STILL EXISTS. IT | | | IS REPRINTED BELOW- PLEASE COMPLY. | | | | | | THE PREVIOUSLY UNCONDITIONED BUILDING NOW BEING | | | CONDITIONED REQUIRES COMPLIANCE WITH THE FLORIDA ENERGY | | | CONSERVATION CODE. PLEASE SEE SECTIONS R101.4.5 AND | | | R101.5.1.1, AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE | | | REPORT FOR THE NEW CONDITIONED SPACE. | | | | | | 2) THE MODEL NUMBER FOR THE AC CONDENSER SHOWN IN THE | | | AC SCHEDULE MODEL NOT MATCH THE MODEL NUMBER ON THE | | | AHRI CERTIFICATE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|