2017-10-27 14:45:361ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17100735
 10/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE WORK DESCRIPTION ON THE PERMIT APPLICATION IS
 INCORRECT- THIS IS NEW AC INSTALLATION AND NOT A CHANGE
 OUT.THE PALM BEACH COUNTY PROPERTY APPRAISOR'S REPORT
 SHOWS NO HEATING OR AC FOR THE RESIDENCE, AND THERE IS
 NO RECORD OF AN AC PERMIT IN THE BUILDING DEPARTMENT
 RECORDS.
  
 2) THE PREVIOUSLY UNCONDITIONED BUILDING NOW BEING
 CONDITIONED REQUIRES COMPLIANCE WITH THE FLORIDA ENERGY
 CONSERVATION CODE. PLEASE SEE SECTIONS R101.4.5 AND
 R101.5.1.1, AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE
 REPORT FOR THE NEW CONDITIONED SPACE.
  
 3) PROVIDE ENGINEERED DETAILS FOR ATTACHING THE
 CONDENSER TO THE CONCRETE PAD- SECTIONS M1305.1.4.1 &
 M1401.4 FBC-14 RESIDENTIAL.
  