| Plan Review Notes For Permit 17100735 |
| Permit Number |
17100735 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-27 14:45:36 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | PERMIT #17100735 | | | 10/27/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE WORK DESCRIPTION ON THE PERMIT APPLICATION IS | | | INCORRECT- THIS IS NEW AC INSTALLATION AND NOT A CHANGE | | | OUT.THE PALM BEACH COUNTY PROPERTY APPRAISOR'S REPORT | | | SHOWS NO HEATING OR AC FOR THE RESIDENCE, AND THERE IS | | | NO RECORD OF AN AC PERMIT IN THE BUILDING DEPARTMENT | | | RECORDS. | | | | | | 2) THE PREVIOUSLY UNCONDITIONED BUILDING NOW BEING | | | CONDITIONED REQUIRES COMPLIANCE WITH THE FLORIDA ENERGY | | | CONSERVATION CODE. PLEASE SEE SECTIONS R101.4.5 AND | | | R101.5.1.1, AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE | | | REPORT FOR THE NEW CONDITIONED SPACE. | | | | | | 3) PROVIDE ENGINEERED DETAILS FOR ATTACHING THE | | | CONDENSER TO THE CONCRETE PAD- SECTIONS M1305.1.4.1 & | | | M1401.4 FBC-14 RESIDENTIAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|