2017-10-23 09:16:47BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROPOSED GATES ON PLAN ARE 3 FEET.
 2. GATES USED AS PART OF A POOL BARRIER SHALL BE A
 MINUMUM OF 4 FEET.
  
 R4502.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED WITH A BARRIER
 COMPLYING WITH SECTIONS R4501.17.1.1 THROUGH
 R4501.17.1.14.
  
 R4501.17.1.1
 THE TOP OF THE BARRIER SHALL BE AT LEAST 48 INCHES
 (1219 MM) ABOVE GRADE, MEASURED ON THE SIDE OF THE
 BARRIER WHICH FACES AWAY FROM THE SWIMMING POOL. THE
 MAXIMUM VERTICAL CLEARANCE BETWEEN GRADE AND THE BOTTOM
 OF THE BARRIER SHALL BE 2 INCHES (51 MM) MEASURED ON
 THE SIDE OF THE BARRIER WHICH FACES AWAY FROM THE
 SWIMMING POOL. WHERE THE TOP OF THE POOL STRUCTURE IS
 ABOVE GRADE, THE BARRIER MAY BE AT GROUND LEVEL OR
 MOUNTED ON TOP OF THE POOL STRUCTURE. WHERE THE BARRIER
 IS MOUNTED ON TOP OF THE POOL STRUCTURE, THE MAXIMUM
 VERTICAL CLEARANCE BETWEEN THE TOP OF THE POOL
 STRUCTURE AND THE BOTTOM OF THE BARRIER SHALL BE 4
 INCHES (102 MM).
  
 R4501.17.1.8
 ACCESS GATES, WHEN PROVIDED, SHALL BE SELF-CLOSING AND
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS
 R4501.17.1.1 THROUGH R4501.17.1.7 AND SHALL BE EQUIPPED
 WITH A SELF-LATCHING LOCKING DEVICE LOCATED ON THE POOL
 SIDE OF THE GATE. WHERE THE DEVICE RELEASE IS LOCATED
 NO LESS THAN 54 INCHES (1372 MM) FROM THE BOTTOM OF THE
 GATE, THE DEVICE RELEASE MECHANISM MAY BE LOCATED ON
 EITHER SIDE OF THE GATE AND SO PLACED THAT IT CANNOT BE
 REACHED BY A YOUNG CHILD OVER THE TOP OR THROUGH ANY
 OPENING OR GAP FROM THE OUTSIDE. GATES THAT PROVIDE
 ACCESS TO THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM
 THE POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING
 GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457
 MM) OF THE RELEASE MECHANISM.
  