| Plan Review Notes For Permit 17100666 |
| Permit Number |
17100666 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-10-23 11:51:17 | 1) SUBMIT TWO COMPLETE SETS OF SPECIFICATIONS FOR THE | | | DOGWASH. THE SPECIFICATIONS CONSIST OF SEVEN PAGES.WPB | | | AMEND. TO FBC SEC. 107.1. | | | 2) THE SANITARY RISER SHOWS A 3" F/A WITH PLUG. WHAT IS | | | THIS AND WHAT IS IT FOR? CLARIFY. | | | 3) WHERE IS THE REQUIRED WATER SUPPLY TO THE UNIT? SHOW | | | WHERE THE WATER CONNECTION IS BEING SUPPLIED FROM, THE | | | SIZE OF THE WATER SUPPLY, SHUTOFF VALVE, & TYPE OF | | | MATERIAL. | | | 4) THE UNIT HAS A HAND HELD SPRAYER. A BACKFLOW | | | PREVENTION DEVICE IS REQUIRED ON THE HAND HELD SPRAYER. | | | 2014 FBC-PLUMBING SEC.424.2. | | | 5) THE SUBMITTED DOCUMENTS HAVE A PLAN STATING" CAR | | | WASH BAY TO DOG WASH SYSTEM CONVERSION". WHAT IS THIS? | | | CLARIFY. | | | 6) SUBMIT A PLAN SHOWING THE LOCATION OF WHERE THIS | | | UNIT WILL BE. WPB AMEND. TO FBC SEC. 107.2.1. | | | 7) IF THERE IS ELECTRICAL AND ALSO ANY STRUCTURAL WORK | | | TO BE DONE FOR THIS DOG WASH, ALL THE PLANS SHALL BE | | | SUBMITTED AS A COMPLETE PACKAGE. WPB AMEND. TO FBC | | | SEC.107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|